TA-Silenzio | TROX GmbH
TA-Silenzio_img_03psd.png
VAV terminal unit Type TA-Silenzio

Easyregler-Compactregler_img_01_2020_01_DEpsd.png
Easy controller, Compact controller

Easy controller, Compact controller

TU-ELAB-Regler_img_01_2020_01_DE__2_psd.psd.link

TROX UNIVERSAL controller,

TROX LABCONTROL controller

TA-Silenzio_img_02psd.png
Rectangular connections on both ends

Rectangular connections on both ends

 

 

00182477_0ai.png
For all upstream conditions

For all upstream conditions

doc_graphic_000009.png
Tested to VDI 6022

Conforms to VDI 6022

TA-Silenzio_img_03psd.png
Easyregler-Compactregler_img_01_2020_01_DEpsd.png
TU-ELAB-Regler_img_01_2020_01_DE__2_psd.psd.link
TA-Silenzio_img_02psd.png
00182477_0ai.png
doc_graphic_000009.png

TA-SILENZIO  

For extract air systems with demanding acoustic requirements and low airflow velocities

Rectangular VAV terminal units for the extract air control in buildings with variable air volume systems, demanding acoustic requirements and low airflow velocities

  • Highly effective integral attenuator
  • Optimised for airflow velocities of 0.7 – 7 m/s
  • High control accuracy, even in case of unfavourable upstream conditions
  • Compact construction with rectangular connections on both ends
  • Electronic control components for different applications (Easy, Compact, Universal, and LABCONTROL)
  • Closed blade air leakage to EN 1751, up to class 4
  • Casing leakage to EN 1751, class C



Optional equipment and accessories

  • Acoustic cladding for the reduction of case-radiated noise
  • Secondary silencer Type TS for the reduction of air-regenerated noise

 


 


 

General Information

Application
  • Rectangular VAV terminal units for use in ventilation and air conditioning systems
  • For controlling, restricting or shutting off airflows in extract air systems with low velocities and demanding acoustic requirements
  • Integral attenuator
  • Closed-loop volume flow control using an external power supply
  • For variable or constant volume flow systems
  • Shut-off by means of switching (by others)
  • Can also be used for differential pressure control with suitable control components


Special features
  • Hygiene tested and certified
  • Direct connection to ductwork
  • Factory set-up or programming and aerodynamic function testing
  • Parameters can also later be set on the control component; additional adjustment device may be necessary


Nominal sizes
  • 125, 160, 200, 250, 315

Variants
  • TA-Silenzio: Extract air unit
  • TA-Silenzio-D: Extract air unit with acoustic cladding
  • Units with acoustic cladding and/or secondary silencer Type TS for very demanding acoustic requirements
  • Acoustic cladding cannot be retrofitted


Parts and characteristics
  • Ready-to-commission unit which consists of mechanical parts and control components
  • Averaging effective pressure sensor for volume flow rate measurement
  • Damper blade
  • Integral attenuator
  • Factory assembled control components complete with wiring and tubing
  • Aerodynamic functional testing on a special test rig prior to shipping of each unit
  • Set-up data is given on a label or volume flow rate scale affixed to the unit
  • High control accuracy even in case of unfavourable upstream conditions


Attachments

  • Easy controller: compact unit with potentiometers
  • Compact controller: compact unit consisting of controller with potentiometers, effective pressure transducer and actuator
  • Universal controller: controller, effective pressure transducer and actuators for special applications
  • LABCONTROL: Control components for air management systems


Useful additions
  • Secondary silencer Type TS


Construction features
  • Rectangular casing
  • Replaceable seals
  • Flanges on both ends for the connection to ductwork
  • Position of the damper blade indicated externally at shaft extension
  • Thermal and acoustic insulation (lining)


Materials and surfaces
  • Casing made of galvanised sheet steel
  • Damper blade and effective pressure sensor made of aluminium
  • Lining is mineral wool
  • Plastic plain bearings

Variant with acoustic cladding (-D)

  • Acoustic cladding made of galvanised sheet steel
  • Lining is mineral wool
  • Rubber elements for the insulation of structure-borne noise

Mineral wool

  • To EN 13501, fire rating class A1, non-combustible
  • RAL quality mark RAL-GZ 388
  • Non-hazardous to health thanks to being highly biosoluble in accordance with the Ordinance on Hazardous Substances and Note Q of the European Directive (EC) No. 1272/2008
  • Faced with glass fibre fabric as a protection against erosion from airflow velocities of up to 20 m/s
  • Inert to fungal and bacterial growth


Standards and guidelines
Fulfils the hygiene requirements of
  • EN 16798, Part 3
  • VDI 6022, Sheet 1
  • DIN 1946, Part 4
Other standards and guidelines in accordance with the hygiene certificate

Casing leakage
  • EN 1751, Class C

Closed blade air leakage
  • EN 1751, Class 4
  • Meets the increased requirements of DIN 1946, Part 4, with regard to the acceptable closed blade air leakage


Maintenance
  • Maintenance-free as construction and materials are not subject to wear

Technical information

Function, Technical data, Quick sizing, Specification text, Order code, Related Products

  • FUNCTION
  • TECHNICAL DATA
  • QUICK SIZING
  • SPECIFICATION TEXT
  • ORDER CODES
  • RELATED PRODUCTS
Schematic illustration of the TA-Silenzio TA-Silenzio_gc_01ai.png

① Effective pressure sensor

② Indicator light

③ Control components, e.g. an Easy controller

④ Damper blade with seal


The VAV terminal unit is fitted with an effective pressure sensor for measuring the volume flow rate.

The control components (attachments) include an effective pressure transducer that transforms the effective pressure into an electric signal, a controller, and an actuator; the control functions can be achieved with an Easy controller, with a Compact controller, or with individual components (Universal).

For most applications, the setpoint value comes from a room temperature controller.

The controller compares the actual value with the setpoint value and alters the control signal of the actuator if there is a difference between the two values.

An integral attenuator reduces the noise that is created by the restriction of the airflow.

 


Nominal sizes 125 – 315
Volume flow rate range 30 – 840 l/s or 108 – 3024 m³ /h
Volume flow rate control range (unit with dynamic differential pressure measurement) Approx. 10 to 100 % of the nominal volume flow rate
Minimum differential pressure5 – 65 Pa
Maximum differential pressure 1000 Pa
Operating temperature10 – 50 °C


Quick sizing tables provide a good overview of the minimum differential pressures, the volume flow rate accuracy and the room sound pressure levels that can be expected. Intermediate values may be achieved by interpolation.

The sound power levels for calculating the sound pressure levels were measured in the TROX laboratory according to DIN EN ISO 5135 - see "Basic information and nomenclature".

Precise results and spectral data for all control components can be calculated with our Easy Product Finder design program. The first selection criteria for the nominal size are the actual volume flow rates qvmin and qvmax.

Volume flow rate ranges and minimum differential pressure values
The minimum differential pressure of VAV terminal units is an important factor in designing the ductwork and in rating the fan including speed control. It must be ensured that for all operating conditions and for all terminal units a sufficient pressure differential is applied to each controller (Δpstat,min). The measurement points for fan speed control must be selected accordingly. The volume flow rates given for VAV terminal units depend on the nominal size and on the control component (attachment) that is installed.

Volume flow rate ranges and minimum differential pressure values
Control component of dynamic measurement principle – Easy (potentiometer)
Attachment: Easy

NSqv [l/s]qv [m³/h]Δpstmin [Pa]Δqv [±%]
1252795238
1257928313236
12513147235635
125183660681234
16042150238
16012444711216
16020774530585
1602891042581134
20060213239
20017663412266
200293105632715
2004101477621385
25075269239
25022380113236
250371133434625
2505181866661215
315126452239
315375134913206
315624224536565
3158723142701085

① Basic unit
② Basic unit with secondary silencer TS


Volume flow rate ranges and minimum differential pressure values
Control component measurement principle – qv Extended
Attachments: BC0, BL0, BM0, BM0-J6

NSqv [l/s]qv [m³/h]Δpstmin [Pa]Δqv [±%]
1252795238
1259433918335
12516258453975
1252308281061944
16042150238
16014953516305
16025692045885
1603621305901774
20060213239
20021175917376
2003631305491085
2005141851982165
25075269239
25026695918326
250458164952955
25064923381031905
315126452239
315448161419296
315771277555855
315109339371091705

① Basic unit
② Basic unit with secondary silencer TS


Volume flow rate ranges and minimum differential pressure values
Control component dynamic measurement principle - qv As standard
Attachments: BUDN, BUDNF, LN0, LK0, XB0, XB4, (B13 *, B1B *)

NSqv [l/s]qv [m³/h]Δpstmin [Pa]Δqv [±%]
1252795238
1258129214256
12513648837685
125190684731334
16042150238
16012846012226
16021477032625
1603001080621214
20060213239
20018165213276
200303109234765
2004251531671485
25075269239
25022982413246
250383137936665
2505371934711305
315126452239
315385138714226
315645232238595
3159043257751165

① Basic unit
② Basic unit with secondary silencer TS

* Discontinued control component


Volume flow rate ranges and minimum differential pressure values
Control component of static measurement principle
Attachments: BUSN, BUSNF, BUSS, XD0, XD4, TUN, TUNF, TUS, TUSD, ELAB (BP3 *, BPG *, BPB *, BB3 *, BBB *)

NSqv [l/s]qv [m³/h]Δpstmin [Pa]Δqv [±%]
1252795238
1258129214256
12513648837685
125190685731334
16042150238
16012846012226
16021477032625
1603001080621214
20060213239
20018165213276
200303109234765
2004251531671485
25075269239
25022982413246
250383137936665
2505371934711305
315126452239
315385138714226
315645232238595
3159043257751165

① Basic unit
② Basic unit with secondary silencer TS

* Discontinued control component

Quick sizing table for sound pressure level
The quick sizing tables are based on generally accepted attenuation and insulation levels. If the sound pressure level exceeds the required level, a larger air terminal unit and/or a silencer or acoustic cladding is required. For more information on the acoustic data, see basic information and nomenclature.

Quick sizing table for air-regenerated noise LPA
Controller, including sound attenuator variants 
(total flow rate range of type)

NSqv [l/s]qv [m³/h]150 Pa500 Pa
1252795< 15< 1520< 15
1259433927173423
12516258433243929
12523082835n.V.4133
1604215015< 1521< 15
16014953529193524
16025692032243828
160362130534n.V.4130
20060213< 15< 1520< 15
20021175925< 153119
200363130529203524
200514185131n.V.3728
25075269< 15< 1520< 15
25026695925< 153119
250458164928183423
250649233831n.V.3726
31512645216< 1522< 15
315448161424< 153018
315771277528193422
3151093393730n.V.3626

Air-regenerated noise LPA [dB(A)] with static differential pressure Δpst of 150 or 500 Pa

① Basic unit

② Basic unit with secondary silencer TS

n.V./abbreviation: Specified static differential pressure Δpst is less than the minimum differential pressure Δpst mi


Quick sizing table case-radiated noise LPA
Controller including acoustic cladding variants 
​​​​​​​(total flow rate range of type)

NSqv [l/s]qv [m³/h]150 Pa500 Pa
1252795< 15< 1516< 15
1259433923223128
12516258429303736
12523082833344140
16042150< 15< 152015
16014953527263432
16025692033334039
160362130537384444
20060213< 15< 1520< 15
20021175927253431
200363130533324038
200514185137374443
25075269< 15< 1521< 15
25026695928253531
250458164934334139
250649233838374543
31512645217< 152518
315448161432303935
315771277538374543
3151093393742424947

Case-radiated noise LPA [dB(A)] with static differential pressure Δpst of 150 or 500 Pa

① Basic unit

② Basic unit with acoustic cladding

Note:
Information on case-radiated noise for combinations of basic unit and optional acoustic cladding and secondary silencer can be found in the Easy Product Finder design program.


Specification text

Rectangular VAV terminal units for variable and constant air volume systems, for demanding acoustic requirements, suitable for extract air, available in 5 nominal sizes. High control accuracy even in case of unfavourable upstream conditions. Ready-to-commission unit which consists of the mechanical parts and the electronic control components. Each unit contains an averaging effective pressure sensor for volume flow rate measurement, a damper blade, and an integral sound attenuator. Factory-assembled control components complete with wiring and tubing. Effective pressure sensor with 3 mm measuring holes, hence resistant to contamination. Both ends suitable for the connection of ducts. Casing with acoustic and thermal insulation. Position of the damper blade indicated externally at shaft extension. The damper blade is factory set to open position, which allows a ventilation airflow even without control; this does not apply to variants with defined safe position NC (normally closed). Meets the hygiene requirements of VDI 6022, DIN 1946, Part 4, as well as EN 13779 and VDI 3803.

Special features
  • Hygiene tested and certified
  • Direct connection to ductwork
  • Factory set-up or programming and aerodynamic function testing
  • Parameters can also later be set on the control component; additional adjustment device may be necessary

Materials and surfaces
  • Casing made of galvanised sheet steel
  • Damper blade and effective pressure sensor made of aluminium
  • Lining is mineral wool
  • Plastic plain bearings

Mineral wool:
  • RAL quality mark RAL-GZ 388
  • To EN 13501, fire rating class A1, non-combustible
  • RAL quality mark RAL-GZ 388
  • Non-hazardous to health thanks to being highly biosoluble in accordance with the Ordinance on Hazardous Substances and Note Q of the European Directive (EC) No. 1272/2008
  • Faced with glass fibre fabric as protection against erosion from airflow velocities of up to 20 m/s
  • Inert to fungal and bacterial growth

Connection
  • With flanges on both ends
  • Both ends suitable for the connection of ducts.

Technical data
  • Nominal sizes: 125 – 315
  • Volume flow rate range: 27 – 872 l/s or 95 – 3142 m³/h
  • Minimum differential pressure: up to 109 Pa (without secondary silencer)
  • Maximum differential pressure: 1000 Pa
  • Closed blade air leakage to EN 1751, class 4. Casing air leakage to EN 1751, class C.

    Equivalence criteria
    • Declaration of hygiene conformity in accordance with VDI 6022, Sheet 1 (01/2018), ÖNORM H 6020 (02/2007) and ÖNORM H 6021 (09/2003)
    • Setting the volume flow rates without adjustment device via qvmin and qvmax potentiometer
    • Electrical connections with screw terminals, no additional terminal boxes required
    • Aerodynamic functional testing of each volume flow controller on test rigs at the factory, before a label is affixed to the controller
    • No inflow lengths required
    • Acoustic data measured to ÖNORM EN ISO 5135:1999
    • Maximum system deviation 5 % at qvmax, without inflow length


    Specification text for attachment
    Variable volume flow control with electronic Easy controller for applying a reference value and capturing an actual value to be integrated with the central BMS.

    • Supply voltage 24 V AC/DC
    • Signal voltages 0 – 10 V DC
    • Possible override controls with external switches using volt-free contacts: CLOSE, OPEN, qᵥmin and qᵥmax
    • Potentiometers with percentage scales to set the volume flow rates qᵥmin and qᵥmax
    • The actual value signal relates to the nominal volume flow rate such that commissioning and subsequent adjustment are simplified
    • Volume flow rate control range: approx. 10 – 100 % of the nominal volume flow rate
    • Clearly visible external indicator light for signalling the functions: Set, not set, and power failure
    • Electrical connections with screw terminals
    • Double terminals for looping the supply voltage, i.e. for the simple connection of voltage transmission to the next controller


    Sizing data
    • q_______________________ [m³/h]
    • Δpst _______________________[Pa]

    Air-regenerated noise
    • LPA _______________________[dB(A)]

    Case-radiated noise
    • LPA _______________________[dB(A)]


    Order code for volume flow control (with Easy attachment)

    TA-SilenzioD / 200 / Easy
    ||||
    1234
    1 Type
    TA-Silenzio VAV terminal unit, extract air
     
    2 Acoustic cladding
    No entry required: None
    D With acoustic cladding
     
    3 Nominal size [mm]

    125, 160, 200, 250, 315
     
    4 Attachments (control component)
    Easy Volume flow controller, dynamic, interface analogue, setting qvmin and qvmax with potentiometers


    Order example: TA–Silenzio/125/Easy
    Acoustic claddingNone
    Nominal size125
    Attachments (control component)Easy volume flow controller, dynamic, setting qvmin and qvmax with potentiometers




    Order code for volume flow control (with VARYCONTROL attachment)
    TA-SilenzioD / 200 / XD4 / V0 / 400 – 1200 [m³/h] / NO
    ||||||||
    12346789
    1 Type
    TA-Silenzio VAV terminal unit, extract air
     
    2 Acoustic cladding
    No entry required: None
    D With acoustic cladding
     
    3 Nominal size [mm]
    125, 160, 200, 250, 315
     
    4 Attachments (control component)
    For example
    BC0 Compact controller
    XD4 Universal controller (VARYCONTROL)
     
    6 Operating mode
    Constant value (one setpoint value)
    V  Variable (setpoint value range)
     
    7 Signal voltage range
    For the actual and setpoint value signals
    0 0 – 10 V DC
    2 2 – 10 V DC
     
    8 Operating values for factory setting
    Volume flow rates [m³/h or l/s]
    qᵥconst. (with operating mode F)
    qᵥmin – qᵥmax (with operating mode V)
     
    9 Damper blade position
    Only with spring return actuators
    NO Power off to OPEN
    NC Power off to CLOSE


    Order example: TA–Silenzio/250/BC0/V0/500–1500 m³/h

    Acoustic claddingNone
    Nominal size250
    Attachments (control component)Compact controller
    Operating modeVariable
    Signal voltage range0 – 10 V DC
    Operating valuesqvmin = 500 m³/h
    qvmax = 1500 m³/h



    Order code for volume flow control (with TROX UNIVERSAL attachment)

    TA-SilenzioD/200/TUNF/RE/M/0/UMZ//NC
    ||||||||||
    12345678910
    1 Type
    TA-Silenzio VAV terminal unit, extract air
     
    2 Acoustic cladding
    No entry: None
    D With acoustic cladding
     
    3 Nominal size [mm]
    125, 160, 200, 250, 315
     
    4 Attachments (control component)
    TROX UNIVERSAL controller with
    TUN Actuator (150 s)
    TUNF Spring return actuator (150 s)
    TUS Fast-running actuator (3 s)
    TUSD Fast-running actuator (3 s) with digital communication interface (TROX HPD)
     
    5 Equipment function

    Room control
    RE Extract air control (Room Exhaust)
     
    6 Volume flow rate setting
    M Master (RMF)
    S Slave
    F Constant flow rate controller
     
    7 Signal voltage range

    0 0 – 10 V DC
    2 2 – 10 V DC
     
    8 Expansion modules

    Option 1: Power supply
    No entry: 24 V AC/DC
    T EM-TRF for 230 V AC
    U EM-TRF-USV for 230 V AC, provides uninterruptible power supply (UPS)
     
    Option 2: Digital communication interface
    No entry: None
    B EM-BAC-MOD-01 for BACnet MS/TP
    M EM-BAC-MOD-01 for Modbus RTU
    I EM-IP: EM-IP for BACnet/IP, Modbus/IP and web server
    R EM-IP with real time clock
     
    Option 3: Automatic zero point correction
    No entry: None
    Z EM-AUTOZERO with solenoid valve
     
    9 Operating values for factory setting
    Volume flow rates [m³/h or l/s], pressure [Pa]
    Master (RMF):
    qvmin: Minimum volume flow rate (room value)
    qvmax: Maximum volume flow rate (room value)
    qvconst_sup: Constant supply air (room value)
    qvconst_ext: Constant extract air (room value)
    qvDiff: Supply air/extract air difference (room value)
     
    Constant value
    qvconst: Constant volume flow rate
     
    Slave
    No entry required
     
    10 Damper blade position
    Only spring return actuators
    NO Power off to OPEN
    NC Power off to CLOSE
     
    Useful additions
    Room control panel
    BE-LCD 40-character display


    Order example: TA-Silenzio-D/315/TUN/RE/S/0/Z
    Acoustic claddingWith
    Nominal size315
    Attachments (control component)Controller TROX UNIVERSAL, static transducer, slow-running actuator
    Equipment functionExtract air control
    Volume flow rate settingSlave
    Signal voltage range0 – 10 V DC
    Expansion of attachmentsWith expansion module EM-AUTOZERO,
    Solenoid valve for automatic zero point correction of measurement point
    Operating valuesNone (slave)



    Order code for differential pressure control (with VARYCONTROL attachment)
    TA-SilenzioD / 200 / XF4 / PRE / V0 / 30 – 60 [Pa] / NO
    |||||||||
    123456789
    1 Type
    TA-Silenzio VAV terminal unit, extract air
     
    2 Acoustic cladding
    No entry required: None
    D With acoustic cladding
     
    3 Nominal size [mm]

    125, 160, 200, 250, 315
     
    4 Attachments (control component)
    For example
    XF0 Compact controller for duct pressure
    XF4 Universal controller for duct pressure (VARYCONTROL)
     
    5 Equipment function/Installation location
    PDE Duct pressure control, extract air
    PRE Room pressure control extract air
     
    6 Operating mode
    Constant value (one setpoint value)
    V  Variable setpoint value range)
     
    7 Signal voltage range

    For the actual and setpoint value signals
    0 0 – 10 V DC
    2 2 – 10 V DC
     
    8 Operating values for factory setting
    With duct pressure control, the differential pressure [Pa] is always an absolute value
    ∆pconst (with operating mode F)
    ∆pmin – ∆pmax (with operating mode V)
     
    9 Damper blade position
    Only with spring return actuators
    NO Power off to OPEN
    NC Power off to CLOSE

    Order example: TA-Silenzio/250/PDE/XF4/F2/500 Pa/NO
    Acoustic claddingNone
    Nominal size250
    Attachments (control component)VARYCONTROL Universal controller duct pressure,
    interface analogue with safe position and display
    Equipment functionDuct pressure control, extract air
    Operating modeConstant value
    Signal voltage range2 – 10 V
    Operating value∆pconst = 500 Pa
    Damper blade positionPower off to OPEN (NO)


    Order code for differential pressure control (with TROX UNIVERSAL attachment)
    TA-SilenzioD/200/TUNF/PRE/MFP/0/UMZ//NC
    ||||||||||
    12345678910
    1 Type
    TA-Silenzio VAV terminal unit, extract air
     
    2 Acoustic cladding
    No entry: None
    D With acoustic cladding
     
    3 Nominal size [mm]
    125, 160, 200, 250, 315
     
    4 Attachments (control component)
    TROX UNIVERSAL controller with
    TUN Actuator (150 s)
    TUNF Spring return actuator (150 s)
    TUS Fast-running actuator (3 s)
    TUSD Fast-running actuator (3 s) with digital communication interface (TROX HPD)
     
    5 Equipment function
    Differential pressure control
    PRE Room pressure control, extract air
    PDE Duct pressure control, extract air
     
    6 Differential pressure setting

    MFP Master, constant pressure control
    MVP Master, variable pressure control
    SFP Slave, constant pressure control
    SVP Slave, variable pressure control
     
    7 Signal voltage range
    0 0 – 10 V DC
    2 2 – 10 V DC
     
    8 Expansion modules
    Option 1: Power supply
    No entry: 24 V AC/DC
    T EM-TRF for 230 V AC
    U EM-TRF-USV for 230 V AC, provides uninterruptible power supply (UPS)
     
    Option 2: Digital communication interface
    No entry: None
    B EM-BAC-MOD-01 for BACnet MS/TP
    M EM-BAC-MOD-01 for Modbus RTU
    I EM-IP for BACnet/IP, Modbus/IP and web server
    R EM-IP with real time clock
     
    Option 3: Volume flow rate measurement
    No entry: None
    V  EM-V Volume flow rate measurement for differential pressure control
     
    Option 4: Automatic zero point correction
    No entry: None
    Z EM-AUTOZERO solenoid valve (only with V)
     
    9 Operating values for factory setting
    Volume flow rate [m³/h or l/s], pressure [Pa]
     
    Slave SVP
    Δpmin: Minimum differential pressure
    Δpmax: Maximum differential pressure
     
    SFP
    Δpconst: Constant differential pressure
     
    Master MFP and MVP – same as slave, but additionally:
    qvmin: Minimum volume flow rate (room value)
    qvmax: Maximum volume flow rate (room value)
    qvconst_sup: Constant supply air (room value)
    qvconst_ext: Constant extract air (room value)
    qvDiff: Supply air/extract air difference (room value)
     
    10 Damper blade position
    Only spring return actuators
    NO Power off to OPEN
    NC Power off to CLOSE
     
    Useful additions
    Room control panel
    BE-LCD 40-character display
     
    Order differential pressure transducer for room or duct pressure control separately e.g.
    PT-699 For room pressure control
    PT-699-DUCT For duct pressure control, including tube and pressure tap 



    Order example: TA-Silenzio-D/315/TUS/PRE/MVP/2/V/10 Pa/30 Pa/750 m³/h/2500 m³/h/0/0/100 m³/h
    Acoustic claddingWith
    Nominal size315
    Attachments (control component)Controller TROX UNIVERSAL, static transducer, fast-running actuator
    Equipment functionRoom pressure control extract air
    Differential pressure settingMaster, variable pressure control
    Signal voltage range2 – 10 V DC
    Expansion of attachmentsVolume flow rate measurement
    Operating valuesPressure range: Δpmin -Δpmax: 10 – 30 PaVolume flow rate range qvmin - qvmax: 750 – 2500 m³/h (room values)
    Constant supply/extract air qvconst_CLOSED, qvconst_Ex:  0 m³/h (room values)
    Supply air/extract air difference: qvDiff: 100 m³/h (room value)


    Order code for room control (with EASYLAB attachment)
    TA-SilenzioD/200/ELAB/S/RE/UMZ/LAB/
    | | | | | | | | |
    1 2 3 4 5 6 8 9 10
    1 Type
    TA-Silenzio VAV terminal unit, extract air
     
    2 Acoustic cladding
    No entry: None
    D With acoustic cladding
     
    3 Nominal size [mm]

    125
    160
    200
    250
    315
     
    4 Attachments (control component)
    ELAB EASYLAB controller TCU3
     
    5 Actuators
    S Fast-running actuator (3 s)
    SD Fast-running actuator (3 s), with digital communication interface (TROX HPD)
     
    6 Equipment function
    Room control
    RE Extract air control (Room Exhaust)
    PC Differential pressure control (Pressure Control)
     
    8 Expansion modules
    Option 1: Power supply
    No entry: 24 V AC/DC
    T EM-TRF for 230 V AC
    U EM-TRF-USV for 230 V AC, provides uninterruptible power supply (UPS)
     
    Option 2: Digital communication interface
    No entry: None
    B EM-BAC-MOD-01 for BACnet MS/TP
    M EM-BAC-MOD-01 for Modbus RTU
    I EM-IP: EM-IP for BACnet/IP, Modbus/IP and web server
    R EM-IP with real time clock
     
    Option 3: Automatic zero point correction
    No entry: None
    Z EM-AUTOZERO Solenoid valve for automatic zero point correction
     
    9 Additional functions
    Without room management function
    LAB Extract air led system (laboratories)
    CLR Supply air led system (clean rooms)
     
    With room management function 
    LAB-RMF Extract air led system
    CLR-RMF Supply air led system
     
    10 Operating values for factory setting
    (only required when room management function is active)
     
    Volume flow rate [m³/h] or [l/s]
     
    Total extract air/supply air of room:
    qv1: Standard mode
    qv2: Reduced operation
    qv3: Increased operation
    qv4: Constant supply air
    qv5: Constant extract air
    qv6: Supply air/extract air difference
    ΔpSet: Setpoint pressure (only with differential pressure control)
     
    Useful additions
    Room control panel (only for units with RMF)
    BE-LCD 40-character display
     
    The differential pressure transducer required for room pressure control (equipment function) has to be ordered separately, e.g.
    PT-699 Measuring range ±50 Pa or ±100 Pa
    PT-GB604 Measuring range ±100 Pa


    Order example: TA-Silenzio/160/ELAB/SD/RE/IZ/LAB
    Acoustic claddingNone
    Nominal size160
    Attachments (control component)EASYLAB controller TCU3
    ActuatorFast-running actuator (3 s), with digital communication interface (TROX HPD)
    Equipment functionExtract air control
    Expansion of attachmentsWith expansion module Type EM-IPBACnet/Modbus-IP interface, web server
    with expansion module EM-AUTOZERO,Solenoid valve for automatic zero point correction of measurement point
    Additional functionExtract air led system for laboratories
    Room management function has been deactivated
    Operating valuesNot required



    Order code for single operation (with EASYLAB attachment)
    TA-SilenzioD/200/ELAB/S/ECE0/UMZ/
    | | | | | | | | |
    1 2 3 4 5 6 7 8 10
    1 Type
    TA-Silenzio VAV terminal unit, extract air
     
    2 Acoustic cladding
    No entry: None
    D With acoustic cladding
     
    3 Nominal size [mm]

    125
    160
    200
    250
    315
     
    4 Attachments (control component)

    ELAB EASYLAB controller TCU3
     
    5 Actuators
    S Fast-running actuator (3 s)
    SD Fast-running actuator (3 s), with digital communication interface (TROX HPD)
     
    6 Equipment function
    Single operation
    EC Extract air controller
     
    7 External volume flow rate setting
    E0 Voltage signal 0 – 10 V DC
    E2 Voltage signal 2 – 10 V DC
    2P Switch contacts (provided by others) for 2 switching steps
    3P Switch contacts (provided by others) for 3 switching steps
    F Volume flow rate constant value, without signalling
     
    8 Expansion modules
    Option 1: Power supply
    No entry: 24 V AC/DC
    T EM-TRF for 230 V AC
    U EM-TRF-USV for 230 V AC, provides uninterruptible power supply (UPS)
     
    Option 2: Digital communication interface
    No entry: None
    B EM-BAC-MOD-01 for BACnet MS/TP
    M EM-BAC-MOD-01 for Modbus RTU
    I EM-IP: EM-IP for BACnet/IP, Modbus/IP and web server
    R EM-IP with real time clock
     
    Option 3: Automatic zero point correction
    No entry: None
    Z EM-AUTOZERO Solenoid valve for automatic zero point correction
     
    10 Operating values for factory setting
    Volume flow rate [m³/h] or [l/s]
    Depending on external volume flow rate setting
    E0, E2: qvmin/qvmax
    2P: qv1/qv2
    3P: qv1/qv2/qv3
    F: qv1


    Order example: TA–Silenzio/200/ELAB/S/EC/E0/300-1000
    Acoustic claddingNone
    Nominal size200
    Attachments (control component)EASYLAB controller TCU3
    ActuatorFast-running actuator (3 s)
    Equipment functionExtract air controller
    External volume flow rate settingVoltage signal 0 – 10 V DC
    Operating valuesqvmin = 300 m³/hqvmax = 1000 m³/h

    Variants, Dimensions and weight, Further product details

    • VARIANTS
    • DIMENSIONS AND WEIGHT
    • PRODUCT DETAILS
    • FURTHER PRODUCT DETAILS

    AV terminal unit TVJ

    • VAV terminal unit for variable extract air volume flow control



    AV terminal unit, variant TVJ-D

    • VAV terminal unit with acoustic cladding for the control of variable extract air volume flows
    • For rooms where the case-radiated noise of the unit is not sufficiently reduced by a false ceiling
    • The ducts for the room under consideration must have adequate acoustic insulation (to be provided by others) on the fan end
    • Acoustic cladding cannot be retrofitted

    Material

    Standard construction

    Order code detailPartMaterial
    -CasingGalvanised sheet steel
    -Effective pressure sensorAluminium
    -Damper bladeAluminium
    -Damper blade sealPolyethylene, PE
    -Shaft and linkageGalvanised steel
    -Plain bearingsPlastic 
    -GearsPlastic, ABS


    Order code detailPartMaterial
    DAcoustic cladding casingGalvanised sheet steel
    DInsulation of structure-borne noisePolyethylene, PE
    DLiningMineral wool according to EN 13501, fire rating Class A1, non combustible
    NS B H L B₁ B₃ H₁ H₃ kg
    125 198 152 1035 232 300 186 236 17
    160 308 152 1035 342 410 186 236 21
    200 458 210 1250 492 560 244 281 32
    250 598 201 1250 632 700 235 311 41
    315 798 252 1250 832 900 286 361 54

    NG B H L B₁ B₃ H₁ H₃ kg
    125 198 152 1035 232 380 186 316 32
    160 308 152 1035 342 490 186 316 38
    200 458 210 1250 492 640 244 361 64
    250 598 201 1250 632 780 235 391 72
    315 798 252 1250 832 980 286 441 91




    Space required for commissioning and maintenance

    Sufficient space must be kept clear near any attachments to allow for commissioning and maintenance. It may be necessary to provide sufficiently sized inspection access openings.

    Space required

    Attachment

    Easy controller












    Easy


    700 300 300

    Compact controller












    BC0, BL0, BM0, BM0-J6, LN0, LK0, XB0, XD0, XF0


    700 300 300

    Universal controller












    BUDN, BUDNF, BUSN, BUSNF, BUSS, BUPN, BUPFN, BURN, BURNF, XB4, XD4, XF4, (B13 *, B1B *, BP3 *, BPB *, BPG *, BB3 *, BBB *, BR3 *, BRB *, BRG *, BS3 *, BSB *, BSG *, BG3, BGB, BH3 *, BHB *)


    700 300 300

    TROX UNIVERSAL












    TUN, TUNF, TUS, TUSD




    700


    350 400

    EASYLAB












    ELAB


    700 350 400

    * Discontinued control component


    Installation and commissioning

    • Any installation orientation (except units with static effective pressure transducer)
    • Return edges of the casing with drilled holes suitable for M10 threaded rods
    • TA-Silenzio-D: For constructions with acoustic cladding, ducts on the room end should have cladding up to the acoustic cladding of the controller


    Upstream conditions

    The volume flow rate accuracy Δqᵥ applies to all upstream conditions.



    VARYCONTROL control components


    AttachmentControlled variableInterfaceEffective pressure transducerActuatorManufacturer
    Easy controller, dynamic
    Easy

    qv

    0 – 10 Vintegralslow-running

    integral
    Compact controller, dynamic
    BC0

    -


    0 – 10 V or 2 – 10 V or MP bus interfaceintegralslow-running

    integral

    BL0 **

    qv

    LonWorks FTT 10 interface

    integralslow-running

    integral
    BM0

    qv



    Modbus RTU/BACnet MS/TP


    integralslow-running

    integral
    BM0-J6

    qv



    Modbus RTU/BACnet MS/TP with RJ12 socket (for X-AIRCONTROL)


    integralslow-running

    integral
    LN0

    qv

    0 – 10 V or 2 – 10 Vintegralslow-running

    integral
    LK0

    qv



    KNX interface


    integralslow-running

    integral
    XB0

    qv

    0 – 10 V or 2 – 10 Vintegralslow-running

    integral
    Compact controller, static
    XD0

    qv

    0 – 10 V or 2 – 10 Vintegralslow-running

    integral
    XF0Δp0 – 10 V or 2 – 10 Vintegral, control range adjustable 25 - 550 Paslow-running

    integral
    Universal controller, dynamic

    B13 *

    qv

    0 – 10 V or 2 – 10 Vintegralslow-running

    separate

    B1B *

    qv

    0 – 10 V or 2 – 10 Vintegralspring return actuator

    separate
    BUDN

    qv

    0 - 10 V or 2 - 10 V or MP bus or Modbus RTU or BACnet MS/TPTPintegralslow-running

    separate
    BUDNF

    qv

    0 - 10 V or 2 - 10 V or MP bus or Modbus RTU or BACnet MS/TPTPintegralspring return actuator

    separate
    XB4

    qv

    0 – 10 V or 2 – 10 Vintegralspring return actuator

    separate
    Universal controller, static

    BP3 *

    qv

    0 – 10 V or 2 – 10 V or MP bus interfaceindividual componentslow-running

    separate

    BPB *

    qv

    0 – 10 V or 2 – 10 V or MP bus interfaceindividual componentspring return actuator

    separate

    BPG *

    qv

    0 – 10 V or 2 – 10 V or MP bus interfaceindividual componentfast-running

    separate

    BB3 *

    qv

    2 – 10 Vindividual componentslow-running

    separate

    BBB *

    qv

    2 – 10 Vindividual componentspring return actuator

    separate

    BR3 *

    Δp0 – 10 V or 2 – 10 V or MP bus interfaceindividual component

    100 Pa
    slow-running

    separate

    BRB *

    Δp0 – 10 V or 2 – 10 V or MP bus interfaceindividual component

    100 Pa
    spring return actuator

    separate

    BRG *

    Δp0 – 10 V or 2 – 10 V or MP bus interfaceindividual component

    100 Pa
    fast-running

    separate

    BS3 *

    Δp0 – 10 V or 2 – 10 V or MP bus interfaceindividual component

    600 Pa
    slow-running

    separate

    BSB *

    Δp0 – 10 V or 2 – 10 V or MP bus interfaceindividual component

    600 Pa
    spring return actuator

    separate

    BSG *

    Δp0 – 10 V or 2 – 10 V or MP bus interfaceindividual component

    600 Pa
    fast-running

    separate

    BG3 *

    Δp2 – 10 Vindividual component

    100 Pa
    slow-running

    separate

    BGB *

    Δp2 – 10 Vindividual component

    100 Pa
    spring return actuator

    separate

    BH3 *

    Δp2 – 10 Vindividual component

    600 Pa
    slow-running

    separate

    BHB *

    Δp2 – 10 Vindividual component

    600 Pa
    spring return actuator

    separate
    BUSN

    qv

    0 - 10 V or 2 - 10 V or MP bus or Modbus RTU or BACnet MS/TPTPintegralslow-running

    separate
    BUSNF

    qv

    0 - 10 V or 2 - 10 V or MP bus or Modbus RTU or BACnet MS/TPTPintegralspring return actuator

    separate
    BUSS

    qv

    0 - 10 V or 2 - 10 V or MP bus or Modbus RTU or BACnet MS/TPTPintegralfast-running

    separate
    BUPNΔp0 - 10 V or 2 - 10 V or MP bus or Modbus RTU or BACnet MS/TPTPintegral

    Control range adjustable 25 – 450 Pa
    slow-running

    separate
    BUPNFΔp0 - 10 V or 2 - 10 V or MP bus or Modbus RTU or BACnet MS/TPTPintegral

    Control range adjustable 25 – 450 Pa
    spring return actuator

    separate
    BURNΔp0 - 10 V or 2 - 10 V or MP bus or Modbus RTU or BACnet MS/TPTPintegral

    Control range adjustable -50 ... -10 Pa or 10 ... 50 Pa
    slow-running

    separate
    BURNFΔp0 - 10 V or 2 - 10 V or MP bus or Modbus RTU or BACnet MS/TPTPintegral

    Control range adjustable -50 ... -10 Pa or 10 ... 50 Pa
    spring return actuator

    separate
    XD4

    qv

    0 – 10 V or 2 – 10 Vintegralspring return actuator

    separate
    XF4Δp0 – 10 V or 2 – 10 Vintegral, control range adjustable 25 - 550 Paspring return actuator

    separate

    * Control component being phased out
    ** Control component to be discontinued - do not include in new projects

    qv Volume flow rate
    Δp Differential pressure
    ① TROX, ② TROX/Belimo, ③ TROX/Gruner, ⑤ Siemens


    TROX UNIVERSAL control components

    AttachmentControlled variableInterfaceEffective pressure transducerActuatorManufacturer
    Universal controller, static
    TUNqv, Δp

    TROX Plug&Play communication system and 0 - 10 V or 2 - 10 V or with optional accessories: LonWorks, Modbus, BACnet, web server

    qv = integral

    Δp = separate
    slow-running

    separate
    TUNFqv, Δp

    TROX Plug&Play communication system and 0 - 10 V or 2 - 10 V or with optional accessories: LonWorks, Modbus, BACnet, web server

    qv = integral

    Δp = separate
    spring return actuator

    separate
    TUSqv, Δp

    TROX Plug&Play communication system and 0 - 10 V or 2 - 10 V or with optional accessories: LonWorks, Modbus, BACnet, web server

    qv = integral

    Δp = separate
    fast-running

    separate
    TUSDqv, Δp

    TROX Plug&Play communication system and 0 - 10 V or 2 - 10 V or with optional accessories: LonWorks, Modbus, BACnet, Webserver

    qv = integral

    Δp = separate

    fast-running with digital communication interface (TROX HPD), separate


    qv Volume flow rate
    Δp Differential pressure
    ① TROX


    LABCONTROL EASYLAB control components

    AttachmentControlled variableInterfaceEffective pressure transducerActuatorManufacturer
    EASYLAB
    ELAB

    qv, Δp *

    TROX plug and play communication system and 0 - 10 V or 2 - 10 V or with optional accessories: Modbus, BACnet, web server

    qv = integral

    Δp = separate

    fast-running, separate



    or



    fast-running with digital communication interface (TROX HPD), separate


    ① TROX

    * Controlled variable depending on the VAV terminal unit type

    • TVR, TVRK: Fume cupboard, room supply air, room extract air, room pressure, single controller
    • TVLK: Fume cupboard, single controller
    • TVJ, TVT: Room supply air, room extract air, room pressure, single controller
    • TVZ, TZ-Silenzio: Room supply air, room pressure, single controller
    • TVA, TA-Silenzio: Room extract air, room pressure, single controller

    Downloads

    product information

    brochures

    certificates

    operation manuals

    production {"X-Frame-Options"=>"SAMEORIGIN", "X-XSS-Protection"=>"1; mode=block", "X-Content-Type-Options"=>"nosniff", "X-Download-Options"=>"noopen", "X-Permitted-Cross-Domain-Policies"=>"none", "Referrer-Policy"=>"strict-origin-when-cross-origin", "Content-Security-Policy"=>"frame-ancestors 'self' https://*.scrivito.com https://punchoutcommerce.com https://www.trox.de https://trox-extern.com https://*.onventis.com http://localhost:63342 http://cerebrum.local", "Strict-Transport-Security"=>"max-age=31536000; includeSubDomains", "Content-Type"=>"text/html; charset=utf-8"}

    Share page

    Recommend this page

    Recommend this page by sending a link by mail.

    Fields marked with an (*) are required fields.

    Share page

    Thank you for your recommendation!

    Your recommendation has been sent and should arrive shortly.

    Contact

    We are here for you

    Please specify your message and type of request
    Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

    Fields marked with an (*) are required fields.

    Contact

    Thank you for your message!

    Your message is send and will be processed shortly.
    Our department for Service-Requests will contact you asap.
    For general question regarding products or services you can also call:
    Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

    Contact

    We are here for you

    Please specify your message and type of request
    Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

    Attachment (max. 10MB)

    Fields marked with an (*) are required fields.