DID-F 

Compact active chilled diffuser with two-sided discharge can be easily combined with other systems for room temperature control such as concrete core or component activation


 

Active chilled beam suitable for freely suspended assembly or installation without suspended ceiling

  • Inexpensive solution for refurbishments and spaces of low floor-to-ceiling height
  • Compact ventilation system for room temperature control with open ceiling design
  • Flexible application – assembly directly below the ceiling slab or freely suspended in the room
  • Short routes due to the connections being positioned on the narrow side with ductwork from the corridor side
  • Individual, manually adjustable air distribution with optionally available air control blades
  • Reduced height thanks to horizontal heat exchanger and simultaneous high thermal load dissipation via the heat transfer fluid water

 

 


General Information

Application


  • Active chilled beams suitable for direct assembly below the ceiling slab or freely suspended in the room
  • A suspended ceiling is not required, which means that these devices can ideally be combined with component activation
  • For an installation height up to preferably 4 m, the room height can be greater
  • Heating with the DID-F is only possible if the devices are installed directly below the ceiling slab and the installation height is ≤ 4 m
  • Adjustable air control blades allow for later manual adjustment of the air discharge direction
  • Preferably with a 2-pipe heat exchanger for cooling; with direct installation below the ceiling slab, a 4-pipe heat exchanger for cooling and heating is also possible
  • Good comfort levels with a low conditioned primary air volume flow rate
  • Energy-efficient solution as water is used for heating and cooling



Special characteristics


  • The optional duct covering enables central installation of the active chilled beam even with a large room depth, whereby the necessary supply lines for air and water are provided with identical covering
  • Manually adjustable air control blades for air direction control enable reduction of vh1 and vl velocities in the occupied zone
  • Horizontal heat exchanger as a 2-pipe system and, for direct installation below the ceiling and a maximum installation height of 4 m, also as a 4-pipe system for heating and cooling
  • Internal nozzle plate with non-combustible punched nozzles
  • Water connections at the narrow side, Ø12 mm Cu pipe with plain tails, with external thread, G½", flat seal or union nut, G½", flat seal



Nominal sizes


  • 1200, 1500, 1800, 2100, 2400, 2700, 3000 mm



Variants

Heat exchanger

  • 2: For 2-pipe systems
  • 4: For 4-pipe systems

Nozzle variants

  • HE: Small
  • S1: Medium
  • S2: Large
  • HP: Extra large



Attachments

Water connections

  • No entry: Ø12 mm pipe with plain tails
  • A1: with G½" external thread and flat seal
  • A2: with G½" union nut and flat seal

Air control blades for subsequent manual adjustment of the supply air flow.


Accessories



  • Duct covering for air and water supply lines, if the active chilled beam is installed deeper in the room or in the centre of the room  (duct covering has the same shape as the DID-F)
  • Heating and cooling valves for controlling the cooling and heating capacity



Useful additions


  • Connecting hoses
  • Control equipment consisting of a control panel including a controller with integral room temperature sensor; valves and valve actuators; and lockshields
  • X-AIRCONTROL control unit with the option of connection to the central building management system



Construction features



  • Duct connection suitable for circular ducts in accordance with EN1506 or EN13180
  • Various fixing systems for suspension with hooks, ropes, threaded rods or directly below the ceiling slab
  • 4 nozzle variants for demand-based induction
  • Induced air grille with offset round perforation
  • Heat transfer fluid connections at the narrow side



Materials and surfaces


  • Casing, induced air grille, spigots, fixing brackets and duct covering made of galvanised sheet steel
  • Nozzle plate made of sheet steel

  • Heat exchanger with copper tubes and aluminium fins
  • Exposed surfaces are powder-coated pure white (RAL 9010) or in any other RAL CLASSIC colour
  • Air control blades made of polypropylene, UL 94, flame retardant (V0)



Standards and guidelines


  • Products are certified by Eurovent (no. 09.12.432) and listed on the Eurovent website
  • Declaration of hygiene conformity to VDI 6022



Maintenance


  • No moving parts, hence low maintenance
  • The heat exchanger can be vacuumed with an industrial vacuum cleaner if necessary
  • VDI 6022, Part 1, applies (Hygiene requirements for ventilation and air-conditioning systems and units)

Technical information

Function, Technical data, Quick sizing, Specification text, Order code

  • FUNCTION
  • TECHNICAL DATA
  • QUICK SIZING
  • SPECIFICATION TEXT
  • ORDER CODE

Active chilled beams provide centrally conditioned primary air (fresh air) to the room and use heat exchangers for additional cooling and/or heating. The primary air is discharged through nozzles (4 different variants) into the mixing chamber; as a result of this, secondary air is induced. Secondary air (room air) is induced via the induced air grille and passes through the horizontal heat exchanger, where it is heated or cooled. Primary and secondary air mix and are then supplied to the room laterally through the supply air slots. The DID-F fulfils this function without a suspended ceiling and can either be installed directly under the ceiling slab or suspended in the room.



 

 



LNPrimary airAir primairePrimary airCooling / 4-pipe systemHeating / 4-pipe system
qvPr [l/s]qvPr [m³/h]Δpt [Pa]LWA [dB(A)]Φges [W]ΦWK [W]tw,r[°C]ΔpW [kPa]Φges = ΦWH [W]tw,r[°C]ΔpW [kPa]
12001243< 1579563417.82.199244.30.2
1200124333128196318.82.1130542.50.2
15001243< 1597677518.22.1121043.10.2
15001243341555116019.32.11575410.2
18001243< 15116391918.62.1142541.80.2
18001243341817134519.92.1182839.50.2
21001243< 151290100519.52.1162240.70.2
210012433519881439212.1206638.20.2
24001243< 151456112819.92.1181839.60.2
24001243352213158721.52.1229136.90.2
27001243< 151605123720.32.1199738.60.2
27001243352422172221.92.1249935.70.2
30001243151749134120.62.1216837.60.2
30001243352628185222.42.1269934.50.2
12001243< 1598272118.12.1108743.80.2
120012433615361030192.1138542.10.2
1500124316122889318.62.1133642.30.2
15001243371875124319.62.1167340.40.2
180012431614461045192.1156041.10.2
18001243372194143820.12.1193938.90.2
21001243171605113719.92.1177339.80.2
21001243382412153221.32.1218837.50.2
24001243191807126820.42.1198038.40.2
24001243392685168421.82.1241936.10.2
27001243211994138920.82.1217237.50.2
27001243402942182422.32.1263534.90.2
30001243232175150221.22.1235436.50.2
30001243413190195522.72.1283833.70.2
12001243< 1588761217.82.192944.70.2
12001243371865110219.22.11398420.2
15001243< 15110675818.22.1114343.40.2
15001243< 382279132519.82.1168740.30.2
18001243< 15131989718.62.1134642.30.2
18001243402686153520.42.1196038.80.2
21001243< 15147698419.42.1153541.20.2
21001243412971162921.62.1221237.30.2
24001243< 151660109819.82.1171640.20.2
24001243423322178922.22.12448360.2
27001243< 151847121120.22.1189439.10.2
27001243433653193622.72.1266734.70.2
30001243162021131520.52.1205938.20.2
30001243453968207123.12.1287333.50.2
12001243< 151119700182.1107243.90.2
12001243442278115019.32.1152041.30.2
1500124317138986118.52.1131142.50.2
150012434527981382202.1183139.50.2
18001243191652101318.92.1153741.20.2
18001243473296159620.62.1211937.90.2
21001243211850110419.82.11747400.2
21001243483656168521.82.1238236.30.2
24001243232089123220.22.1195138.80.2
24001243504043183822.32.12617350.2
27001243262314135020.62.1214137.70.2
27001243504210193722.72.12788340.2
300012432825391465212.1232536.70.2
30001243504291201222.92.1292833.20.2

① Nozzle variant

Sound power level

 
Reference values

ParameterCoolingHeating
tR26 °C22 °C
tPr16 °C22 °C
tWV16 °C50 °C
qv,W (LN 900 – 1800 mm)300 l/h150 l/h
qv,W (LN 2100 – 3000 mm)250 l/h150 l/h


Specification text

Active chilled beams of type DID-F with two-way air discharge are suitable for freely suspended or direct installation below the ceiling slab and offer optimum comfort thanks to the ideal discharge angle and maximum induction. The active chilled beam can be used on its own or as the perfect extension to a concrete activation since it has a positive impact on the thermal output supplied to the room. This air-water system does not require a false ceiling, and the maximum installation height should preferably not exceed 4 m. 3 different assembly kits are optionally available for fixing, but with 4 different assembly options, and these are installed using standard fixing materials. This enables fast, straightforward installation, depending on the structural conditions. The sizing of the technical data can be varied by choosing one of four possible nozzle sizes. The nozzles are punched into the nozzle plate and are non-combustible. The primary air flow rate can be low for hygiene and energy reasons. Working in conjunction with the horizontal heat exchanger, this enables the dissipation of large heating and cooling loads. The water connections positioned on the narrow side are optionally available as plain tails, G½" external thread with flat seal or G½" union nut. The primary air connection is on the same connection side as the water connections and is available with a nominal diameter of 125 mm, 160 mm or 200 mm. This allows for direct connection of devices e.g. via the corridor side, avoiding complex ducting within the room. Circular ducts in accordance with EN 1506 or EN 13180 can be installed directly. Owing to the decreasing apertures of the induced air grille, the DID-F fits perfectly into its surroundings. The optional air control blades allow for air distribution to be adjusted manually at any time.


Special features

  • The optional duct covering enables central installation of the active chilled beam even with a large room depth, whereby the necessary supply lines for air and water are provided with identical covering
  • Manually adjustable air control blades for air direction control enable reduction of vh1 and vl velocities in the occupied zone
  • Horizontal heat exchanger as a 2-pipe system and, for direct installation below the ceiling and a maximum installation height of 4 m, also as a 4-pipe system for heating and cooling
  • Internal nozzle plate with non-combustible punched nozzles
  • Water connections at the narrow side, Ø12 mm Cu pipe with plain tails, with external thread, G½", flat seal or union nut, G½", flat seal



Materials and surfaces

  • Casing, induced air grille, spigots, fixing brackets and duct covering made of galvanised sheet steel
  • Nozzle plate made of sheet steel

  • Heat exchanger with copper tubes and aluminium fins
  • Exposed surfaces are powder-coated pure white (RAL 9010) or in any other RAL CLASSIC colour
  • Air control blades made of polypropylene, UL 94, flame retardant (V0)


Technical data

  • Length = nominal length: 1200, 1500, 1800, 2100, 2400, 2700 and 3000 mm
  • Height: 221, 256, 296 mm
  • Width: 400 mm
  • Diameter of spigot: 123, 158 and 198 mm
  • Cooling capacity up to 4290 W
  • Heating capacity up to 2920 W
  • Max. operating pressure, water side: 6 bar
  • Max. operating temperature: 75 °C



DID-F4S2A2 / 1200 x 123 x 1000 / A / LE / P1 – RAL …
||||||||||
12345678910

1 Type
DID-F Active chilled beam 

2 Heat exchanger
2 2-pipe4 4-pipe
 
3 Nozzle variant
HE small
S1 medium
S2 large
HP Extra large 

4 Water connections
No entry: Ø12 mm pipe with plain tails
A1 With G½" external thread and flat seal

A2 With G½" union nut and flat seal 

5 Nominal lengths [mm]
1200, 1500, 1800, 2100, 2400, 2700, 3000 

6 Primary air spigot
123
158
198 

7 Duct covering
No entry: none
1000 Length 200 – 2900 mm 

8 Fixing variant
No entry required: assembly using threaded blind holes M6
A Assembly kit for assembly directly under the ceiling slab
B Assembly kit for freely suspended assembly with fixing brackets
C Assembly kit for freely suspended assembly with suspension lugs 

9 Air control elements
No entry: none
LE With air control blades 

10 Exposed surface
No entry: powder-coated RAL 9010, pure white
P1 Powder-coated, specify RAL CLASSIC colour     


Order example: DID-F–2–S1/1500×123×
Heat exchanger2-pipe system
Nozzle variantMedium
Water connectionsØ12 mm pipe, plain tails
Length of unit1500 mm
Primary air spigot, diameter123 mm
Duct coveringNone
Fixing variantThreaded blind holes M6
Air control elementsNone
Exposed surfacepowder-coated in RAL 9010 GE 50, pure white


Variants, Dimensions

  • Variants
  • DIMENSIONS

DID-F with duct connection

Application

  • Duct covering provides a visually attractive covering for the supply lines provided by others if the DID-F is assembled deeper in the room
  • Duct coverings can be ordered in the lengths 200 – 2900 mm
  • Duct covering can be integrated into the room so that it is visually inconspicuous, as it has a similar geometry to the DID-F

Materials and surfaces

  • Duct covering made of galvanised sheet steel
  • Exposed surfaces are powder-coated pure white (RAL 9010) or in any other RAL CLASSIC colour



Water connections Ø12 mm pipe, plain tails 
Water connections A1 G½" external thread and flat seal Water connections A2 G½" union nut and flat seal

Application

  • Water connections form the interface between the active chilled beam and the duct network provided by others
  • To find the best form of transition for the project, there are 3 different water connections available
  • Ø12 mm Cu pipe with plain tails – connection is particularly suitable for a direct connection to the copper pipe network; all the usual connection methods can be used here such as soldering, press-fit and push-fit
  • A1, G1/2" external thread and flat seal – water connection is particularly suitable for connection with union nuts, which creates a detachable connection
  • A2, G1/2" union nut and flat seal – this is also a detachable solution and is particularly suitable for direct connection of control valves and shut-off valves
  • All connections provided by others must be tested under pressure once installed and checked for tightness

Nominal sizes

  • 1200, 1500, 1800, 2100, 2400, 2700, 3000 mm

Useful additions

  • Type FS connecting hoses are available with connections for all water connection variants


Front blind / Rear blind hole suspension
Variant A, front insert suspension / rear insert suspension
Variant B, front bracket / rear bracket suspension

Variant C, front / rear lug suspension

Application

  • Type DID-F active chilled beams suitable for direct installation below the ceiling slab or freely suspended in the room
  • A suspended ceiling is not required, which means that these devices can ideally be combined with component activation
  • For an installation height up to preferably 4 m, the room height can be greater
  • Adjustable air control blades allow for later manual adjustment of the air discharge direction
  • Preferably with a 2-pipe heat exchanger for cooling; with direct installation below the ceiling slab, a 4-pipe heat exchanger for cooling and heating is also possible
  • Good comfort levels with a low conditioned primary air volume flow rate
  • Energy-efficient solution as water is used for heating and cooling

ØD

H




HS




123




221




147




158




256




164.5




198




296




184.5







K




200 – 2900 in mm increments




L




1200, 1500, 1800, 2100, 2400, 2700, 3000 mm





Dimensions – 1 horizontal spigot
LN
1200158123 & 198
1500158123 & 198
1800158123 & 198
2100158123 & 198
2400158123 & 198
2700158123 & 198
3000158123 & 198
1200158123 & 198
1500158123 & 198
1800158123 & 198
2100158123 & 198
2400158123 & 198
2700158123 & 198
3000158123 & 198
1200198158
1500198158
1800198158
2100198158
2400198158
2700198158
3000198158
1200198158
1500198158
1800198158
2100198158
2400198158
2700198158
3000198158

Project-specific solutions

  • Project-specific solutions

Air-water systems offer both standard and project-specific solutions such as, for example, the combination with light or vertically positioned spigots. If required, we can also develop a suitable project-specific variant for your project. Simply contact your TROX contact partner.

Downloads

product information

certificates

Share page

Recommend this page

Recommend this page by sending a link by mail.

Fields marked with an (*) are required fields.

Share page

Thank you for your recommendation!

Your recommendation has been sent and should arrive shortly.

Contact

We are here for you

Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

Contact

We are here for you

Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

Attachment (max. 10MB)

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265