FK2-EU

For diverse applications


Rectangular fire damper for the isolation of duct penetrations between fire compartments, for a variety of installation situations, available in many sizes and constructions

 Nominal sizes 200 × 100 – 800 × 200 mm, in increments of 1 mm

  • Low differential pressure and sound power level
  • Integration into the central BMS with TROXNETCOM
  • Universal installation options

 
Optional equipment and accessories

  • Electric actuator 24 V/230 V
  • Release temperature 72/95 °C
  • Duct smoke detectors

FK2-EU_img_04.psd.png

Application

Application


  • TROX fire dampers of type FK2-EU with CE marking and declaration of performance, for the isolation of duct penetrations between two fire compartments by automated closing in the event of a fire
  • To prevent the propagation of fire and smoke through ductwork to adjacent designated fire compartments

Special characteristics


  • Declaration of performance in accordance with European Construction Products Regulation
  • Classification according to EN 13501-3 up to EI 120 (ve, ho, i ↔ o) S
  • Complies with the requirements of EN 15650
  • Tested for fire resistance properties in accordance with EN 1366-2 (300 Pa and 500 Pa negative pressure)
  • Certified mortar-based installation with reduced distances of 40 mm to supporting components or 60 mm between two fire dampers (flange to flange)
  • Surrounding gap dimensions in the mortar-based installation with mortar up to 225 mm permitted
  • Two inspection accesses with bayonet fixing for single-handed operation
  • Hygienic requirements are fulfilled in accordance with VDI 6022-1, VDI 3803-1, DIN 1946-4, DIN EN 13779 as well as Önorm H 6020 and H 6021 and SWKI
  • Corrosion protection according to EN 15650 in connection with EN 60068-2-52
  • Closed blade air leakage according to EN 1751, class 2
  • Casing air leakage according to EN 1751, class C; (B + H) ≤ 700, class B
  • Low differential pressure and sound power level
  • Any airflow direction
  • Integration into the central building management system with the international standard fire damper system in accordance with IEC 62026-2 with AS interface is possible


Classification


  • Class of performance up to EI 120 (ve, ho, i ↔ o) S according to EN 13501-3

Nominal sizes


  • B × H: 200 × 100 – 800 × 200 mm (in increments of 1 mm)
  • L: 305 mm or 500 mm

Description

Nominal sizes
  • B × H: 200 × 100 – 800 × 200 mm (in increments of 1 mm)
  • L: 305 mm or 500 mm

Parts and characteristics

  • Release temperature 72 °C or 95 °C (for use in warm air ventilation systems)
  • Single-handed operation

Attachments
  • Limit switch for damper blade position indication
  • Spring return actuator for 24 V AC/DC or 230 V AC supply voltage
  • Network module for the integration with AS-i or LON networks
  • Spring return actuator and pre-wired duct smoke detector, 24 V or 230 V supply voltage
  • All attachments can be retrofitted

Casing:

• Galvanised sheet steel

Damper blade:
• Special insulation materia

Standards and guidelines

• Construction Products Regulation
▪ EN 15650 Ventilation for buildings – Fire dampers
▪ EN 1366 Fire resistance tests for service installations – Fire dampers
▪ EN 13501 Fire classification of construction products and building elements
▪ EN 1751 Ventilation for buildings – Air terminal devices



Maintenance
▪ The functional reliability of the fire damper must be tested at least every six months; this has to be arranged by the owner of the ventilation system; functional tests must be carried out in compliance with the basic maintenance principles stated in EN 13306 and DIN 31051. If two consecutive tests, one 6 months after the other, are successful, the next test can be conducted one year later.
▪ A functional test involves closing the damper blade and opening it again; with a spring return actuator this can be done via remote control
▪ Fire dampers must be included in the regular cleaning schedule for the ventilation system
▪ For details on functional tests, maintenance and inspection refer to the installation and operating manual

Technical data

▪ Nominal sizes: 200 × 100 to 800 × 200 mm
▪ Casing lengths: 305 and 500 mm
▪ Volume flow rate range: up to 1920 l/s / up to 6900 m³/h
▪ Differential pressure: up to 2000 Pa
▪ Temperature range: -20 – 50 °C
▪ Upstream velocity (with same inflow and outflow): standard construction ≤ 8 m/s, design with spring return actuator ≤ 12 m/s

Classification
  • Class of performance up to EI 120 (ve, ho, i ↔ o) S according to EN 13501-3

Technical information

Function, Technical Data, Quick sizing, Specification Text, Order Code

  • FUNCTION
  • TECHNICAL DATA
  • QUICK SIZING
  • SPECIFICATION TEXT
  • ORDER CODE

 

 



Nominal sizes

200 × 100 – 800 × 200 mm

Casing lengths

305 and 500 mm

Volume flow rate range

up to 1920 l/s or 6900 m³/h

Differential pressure range

Up to 2000 Pa

Temperature range 1, 3

-20 °C to 50 °C

Release temperature

72 °C or 95 °C (for warm air ventilation systems)

Upstream velocit ²

≤ 8 m/s with standard construction; ≤ 12 m/s  with spring return actuator


¹ Temperatures may differ for units with attachments. Details for other applications are available on request.
² Data applies to uniform upstream and downstream conditions for the fire damper.
³ Condensation and the intake of humid fresh air have to be avoided as otherwise operation will be impaired or not be possible.

Free area and resistance coefficient, width 200 – 800 mm

H [mm]B [mm]
200250300350400450500550600650700750800
100A [m²]0.0130.0160.020.0230.0270.030.0340.0370.0410.0440.0480.0510.055
100ζ1.050.960.880.830.780.750.710.690.660.640.620.610.59
125A [m²]0.0220.0280.0340.040.0460.0520.0580.0640.070.0760.0820.0880.094
125ζ0.930.850.780.730.690.660.630.610.590.570.550.540.52
150A [m²]0.0310.040.0480.0570.0650.0740.0820.0910.0990.1080.1160.1250.133
150ζ0.850.770.710.670.630.60.580.550.540.520.50.490.48
160A [m²]0.0240.030.0370.0430.050.0560.0630.0690.0760.0820.0890.0950.102
160ζ0.660.60.550.520.490.470.450.430.410.40.390.380.37
200A [m²]0.0310.040.0480.0570.0650.0740.0820.0910.0990.1080.1160.1250.133
200ζ0.740.670.620.580.550.520.50.480.470.450.440.430.41

① Parameter 


 

 

 

 

 

 



Quick sizing tables provide a good overview of the volume flow rates with different sound power levels as well as of differential pressures of up to 35 Pa. Approximate intermediate values can be interpolated. Precise intermediate values can be calculated with our Easy Product Finder design programme.

Volume flow rate qv For differential pressure Δpst < 35 Pa

H [mm]LWA [dB(A)]B [mm]
200250300350400450500550600650700750800
10035390484577668759849938102711161205129313801468
1253550762774586297810931208132214351548166017721883
150356197649071048118813261464160117371873200821422276
1603572889710631227139015501710186920272185234124972653
20035835102812161402158617691950213023092487266428413017

 Volume flow rate qv For differential pressure Δpst < 35 Pa

H [mm]LWA [dB(A)]B [mm]
200250300350400450500550600650700750800
10045570707841975110712391369149916291758188620142142
1254574091510881258142715951762192820942258242225852748
15045904111513231529173319352136233625342732292931263322
160451063130915521791202822622496272729583188341636443871
200451219149917752046231425802845310733683628388741454402

Sizing example

Given data
Volume flow rate: 1000 m³/h
Maximum height: 100 mm
Sound power level: 35 dB(A)

Quick sizing
FK2-EU/550×100×500




Specification text

Fire damper in line with the European product standard DIN EN 15650 in square or rectangle construction style with two large inspection accesses that can be operated without tools. Tested for fire resistance properties according to DIN EN 1366-2 (300 Pa and 500 Pa negative pressure), with CE label.

The fire damper manufacturer's declaration of performance (DoP) provides proof of the respective installation conditions. e.g. inside, in front of, at and remote from walls or ceilings, along with the basic characteristics such as size, support structure, design and installation type and the respective classes of performance in accordance with the classification standard DIN EN 13501-3.

The ready-to-use units contain a release mechanism and an interchangeable, fire-resistant damper blade that can be arranged horizontally or vertically depending on the use. Depending on application, classified from

EI 30 (ve, ho i ↔ o) S to EI 120 (ve, ho i ↔ o) S.

 


Suitable for:


         Mortar-based installation


  • In solid walls, lightweight partition walls, compartment walls, safety partition walls and radiation protection walls
  • with installation kit for flexible ceiling joint in solid walls
  • In shaft walls with metal support structures or steel support structures
  • In timber stud walls and half-timbered constructions In solid wood and cross laminated timber walls
  • In and on solid walls and in combination with timber beam, solid wood and modular ceilings (System Cadolto)

    Dry mortarless installation

     
  • In lightweight partition walls, compartment walls, safety partition walls and radiation protection walls with metal support structures or steel support structures
  • In timber stud walls and half-timbered constructions In solid wood and CLT (cross laminated timber) walls
  • In shaft walls with metal support structure or steel support structure
  • Remote from solid walls and ceiling slabs, with installation kit
  • Remote from lightweight partition walls (wall penetration)

    Fire batt installation

     
  • In solid walls, lightweight partition walls, fire protection walls, safety partition walls and radiation protection walls with metal support structure or steel support structure and timber stud, half-timbered construction, solid wood and cross laminated timber walls
     

Size dimensions from (B x H) 200 mm x 100 mm to 800 mm x 200 mm, in increments of 1 mm. Optimised, low-leakage casing, up to tightness class C in accordance with DIN EN 1751 with reduced differential pressure and sound power level, made from galvanised sheet steel. Corrosion protection according to DIN EN 15650 in connection with DIN EN 60068-2-52. The hygiene requirements are fulfilled in accordance with VDI 6022-1, VDI 3803-1, DIN 1946-4, DIN EN 13779, as well as Önorm H 6020 and H 6021 and the SWKI. Casing lengths 305 mm or 500 mm with 30 mm (L=500 mm) flange for connecting to ducting made of non-combustible or combustible materials. Thermal release for 72 °C or 95 °C (warm air ventilation) with fusible link or thermoelectrically with spring return actuator, test switch/push button and control LED. The designs with brushless spring return actuators for opening and closing the fire damper – also when the ventilation system is running and independent of the nominal size – are particularly suited for function testing or the daily shut-off of cable sections. Retrofit of spring return actuators without modification of the rod is possible from the outside.

Special characteristics
  • Declaration of performance in accordance with European Construction Products Regulation
  • Classification according to EN 13501-3 up to EI 120 (ve, ho, i ↔ o) S
  • Complies with the requirements of EN 15650
  • Tested for fire resistance properties in accordance with EN 1366-2 (300 Pa and 500 Pa negative pressure)
  • Certified mortar-based installation with reduced distances of 40 mm to supporting components or 60 mm between two fire dampers (flange to flange)
  • Surrounding gap dimensions in the mortar-based installation with mortar up to 225 mm permitted
  • Two inspection accesses with bayonet fixing for single-handed operation
  • Hygienic requirements are fulfilled in accordance with VDI 6022-1, VDI 3803-1, DIN 1946-4, DIN EN 13779 as well as Önorm H 6020 and H 6021 and SWKI
  • Corrosion protection according to EN 15650 in connection with EN 60068-2-52
  • Closed blade air leakage according to EN 1751, class 2
  • Casing air leakage according to EN 1751, class C; (B + H) ≤ 700, class B
  • Low differential pressure and sound power level
  • Any airflow direction
  • Integration into the central building management system with the international standard fire damper system in accordance with IEC 62026-2 with AS interface is possible

Materials and surfaces

Casing:

  • Galvanised sheet steel

Damper blade:

  • Special insulation material

Technical data

  • Nominal sizes: 200 × 100 to 800 × 200 mm
  • Casing lengths: 305 and 500 mm
  • Volume flow rate range: up to 1920 l/s / up to 6900 m³/h
  • Differential pressure: up to 2000 Pa
  • Temperature range: -20 – 50 °C
  • Upstream velocity (with same inflow and outflow): standard construction ≤ 8 m/s, design with spring return actuator ≤ 12 m/s

FK2-EUW / DE / 400 × 125 × 500 / ES / A0 / Z43
|||||||
1234567


1 Type
FK2-EU
Fire damper

2 Construction
No entry required: standard construction
W 2) With fusible link 95 °C (only for warm air ventilation systems)
B3) With coated fusible link 72 °C
WB3) With coated fusible link 95 °C (only for warm air ventilation systems)

3 Country of destination
DE
Germany
AT Austria
CH Switzerland
NL Netherlands

4 Nominal size [mm]
B × H × L

5 Accessories 1
No entry: none
ES1)
GM1)

6 Accessories 2
No entry: none
0A – FR

7 Attachments
Z00 – ZA14

1) Only for FK2-EU with L = 500 mm
2) Not combinable with Z...RM and ZA12
3) Only for attachment Z00 - Z03

 

Order example: FK2-EU-W/DE/600x200x500/ES/A0/Z43
TypeFK2-EU
Construction variant Casing (galvanised)
Release temperature95 °C
Country of destinationGermany
Nominal size600 x 200 x 500 mm
Accessories 1Installation kit ES
Accessories 2Cover grille on operating side
AttachmentSpring return actuator 230 V AC

 

Note:
For further information relevant to design, in particular information on installation situations, please refer to the operating and installation manual.


Variants, Dimensions, Product details

  • Variants
  • DIMENSIONS
  • PRODUCT DETAILS

Nominal sizes

  • B × H: 200 × 100 – 800 × 200 mm (Zwischengrößen in 1 mm Schritten bestellbar)
  • L: 305 mm oder 500 mm

Nominal sizes

  • B × H: 200 × 100 – 800 × 200 mm (Zwischengrößen in 1 mm Schritten bestellbar)
  • L: 305 mm oder 500 mm

Nominal sizes

  • B × H: 200 × 100 – 800 × 200 mm (Zwischengrößen in 1 mm Schritten bestellbar)
  • L: 305 mm oder 500 mm

H [mm]
200250300350400450500550600650700750800
10044556677889910
125455667788991010
1504556778899101011
16045667788910101111
200566778991010111212
,
H [mm]
200250300350400450500550600650700750800
1005566778899101011
12556677889910101111
150566788991010111112
1606677889101011111212
20067788910101111121313
,
H [mm]B [mm]
200250300350400450500550600650700750800
100666788891010101112
1256677889101011111212
1506778899101111121213
16067789910101111121213
200778991010111212131314

Installation and commissioning

Installation is carried out according to the installation and operating manual.

Mortar-based installation:

  • In solid walls and ceiling slabs
  • In non-load-bearing solid walls with flexible ceiling joint: with installation kit GM
  • In lightweight partition walls and compartment walls with metal support structure and cladding on both sides
  • In timber stud walls and half-timbered constructions
  • On wooden beam ceilings
  • On modular ceilings (Cadolto system)

Dry mortarless installation:

  • In lightweight partition walls and compartment walls with metal support structure and cladding on both sides: with installation kit ES
  • In lightweight partition walls with metal support structure, cladding on both sides and flexible ceiling joint: with installation kit GL100
  • In timber stud walls and half-timbered constructions with cladding on both sides: with installation kit ES
  • In shaft walls with or without metal support structure and cladding on one side: with installation kit ES
  • On the face of solid walls: with installation kit WA, for size L = 375 or 500 mm
  • Adjacent to solid walls: with installation kit WV
  • Remote from solid walls: with installation kit WE
  • Remote from solid ceiling slabs: with installation kit WE (in horizontal ducts)

Downloads

product information

certificates

operation manuals

Share page

Recommend this page

Recommend this page by sending a link by mail.

Fields marked with an (*) are required fields.

Share page

Thank you for your recommendation!

Your recommendation has been sent and should arrive shortly.

Contact

We are here for you

Visual contact Visual contact

Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Visual contact Visual contact

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

Contact

We are here for you

Visual contact Visual contact

Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

Attachment (max. 10MB)

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Visual contact Visual contact

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call: