XSMB0-J6 

Control component with static transducer and Modbus RTU interface for X-AIRCONTROL

Compact device for VAV terminal unit TVE and TVE-Q
■ Controller, static differential pressure transducer and actuator in one casing
■ Use in ventilation and air conditioning systems, for clean and contaminated air
■ Simple RJ12 connection socket for supply voltage and network
■ Compatible with the X-AIRCONTROL zone module Modbus
■ Volume flow rates qvmin and qvmax are pre-set at the factory and saved in the controller as variable parameters
■ High data transparency via standardised bus communication RS485 

  • Modbus RTU: Register access
■ Setpoint value settings, override controls, parameter adjustment via Modbus register
■ Integrated display for volume flow rate display, operating status display and setting of operating parameters
■ Service access for manual adjustment devices and PC configuration software

General information

Application
  • All-in-one control device for VAV terminal units type TVE and TVE-Q
  • Static differential pressure transducer, controller electronics and actuator combined in one casing
  • For clean and contaminated air in ventilation and air conditioning systems:
    • E.g. in the extract air area with dust, fluff, sticky or moist components
    • Application examples: Extract air from changing rooms and shower areas as well as hospital bedrooms, production facilities and corridor areas - e.g. in schools
  • Various control options based on corresponding setpoint specification
  • Room temperature controller, management and control equipment (MCE), air quality controller and others control the variable volume flow regulation by specifying setpoint values via communication interface
  • Override control for activating qvmin, qvmax, shut-off, OPEN position, possible via the Modbus register
  • The actual volume flow rate value is available as a network data point
  • Damper blade position, e.g. for fan optimisation, is available as a network data point

Control strategy
  • The volume flow controller works independently of duct pressure
  • Pressure fluctuations do not cause any permanent volume flow deviations
  • A dead zone (hysteresis), within which the damper blade is not moved, ensures stable regulation
  • The volume flow range for the controller is factory-set (qvmin: minimum volume flow, qvmax: maximumvolume flow)
  • Operating parameters are defined in the order code and factory-set

Operating modes

Modbus (M):

  • Setpoint specification via X-AIRCONTROL

Communication interface
  • Modbus RTU, RS485
  • Data points see Modbus register list

Parts and characteristics
  • Transducer based on static measurement principle
  • Overload-protected actuator
  • RJ12 connection socket with cover
  • Display and control elements for easy menu navigation
  • Menu navigation for adjusting operating parameters
  • Menu navigation for customising the communication interface
  • Service interface

Construction
  • TR0VM-024T-10I-DS12-BN with RJ12 connection socket
  • Can only be used for type TVE and TVE-Q

Commissioning

  • As the volume flow rates are factory-set, the air terminal units must be installed only at the designated locations
  • Operating parameters can be adjusted by the client (using the display, an adjustment device, or the Modbus register)

Useful additions
  • Adjustment device type GUIV3-M (order code AT-VAV-G3)
  • Room control X-AIRCONTROL with zone module Modbus type X-AIR-ZMO-MOD

Technical information

  • Function
  • SPECIFICATION TEXT
  • ORDER CODE
  • TECHNICAL DATA
XSMB0-J6-Function

1 Differential pressure transducer
2 Actuator
3 Control component
4 Setpoint via Modbus
5 Shaft with effective pressure channel

Volume flow controllers are characterised by a closed control loop for controlling the volume flow, i.e. measuring - comparing - adjusting.
The volume flow is obtained by measuring a differential pressure.
This is done via a differential pressure sensor. The integrated differential pressure transducer converts the differential pressure into a voltage signal. The actual volume flow value is available as a data point. Due to the factory-set values, 100% always equals the nominal volume flow rate (qvnom).
The volume flow setpoint is specified by a higher-level controller (e.g. room temperature controller, air quality controller, MCE).
Variable volume flow control can be set between qvmin and qvmax. It is possible to override the room temperature control by override control, e.g. via a shut-off.
The controller compares the volume flow setpoint with the current actual value and adjusts the internal actuator, according to the control deviation.

This specification text describes the general properties of the product. Texts for variants can be generated with our Easy Product Finder design programme.

Category

  • Compact controller for volume flow

Anwendung

  • Control of a constant or variable volume flow setpoint
  • Electronic controller for connecting a reference value and tapping an actual value for integration into a Modbus-based MCE
  • The actual value is referenced to the nominal volume flow, simplifying commissioning and subsequent adjustment

Area of application

  • Static transducer for contaminated air in ventilation and air conditioning systems

Actuator

  • Integrated; slow-running (travel time 100 s for 90°)

Installation orientation

  • Either direction

Connection

  • RJ12 connection socket with rubber cap cover, suitable for TROX X-AIRCONTROL zone module X-AIR-ZMO-MOD
  • connection terminals are optional

Supply voltage

  • 24 V AC/DC

Interface/signalling

  • Modbus RTU (RS485) factory-activated

Interface information

  • BACnet or Modbus: volume flow setpoint and actual value signal, damper blade position, override control among other options

System connections

  • Modbus connection for optional expansions, e.g. TROX XAIRCONTROL zone module Modbus

Special functions

  • Clearly visible external indicator light for signalling the functions: controlled, not controlled, and power failure
  • Display for actual values, parameter setting, and for test functions
  • Activation of override control functions qvmin, qvmaxclosed, Open via Modbus commands

Parameter setting

  • Specific parameters for VAV terminal unit are factory-set
  • Operating values: qvmin, qvmax and interface type Modbus factory-set
  • Subsequent adjustment via display and control element directly on the device or with optional tools:
    • Adjustment device, PC software (each wired)

Factory condition

  • Functional test under air using reference measurement on a regularly validated test rig in accordance with DIN EN ISO 9001 to check the function and control accuracy of the complete volume flow controller
  • Adjustment of the device-specific parameters under air by reference measurement on a regularly validated test rig if in accordance with DIN EN ISO 9001
  • The test report of the factory parameterisation, functional test and adjustment must be made available after delivery of the volume flow controller

Equivalence criteria
  • The test report of the factory parameterisation, functional test and adjustment under air by reference measurement on a regularly validated test rig in accordance with DIN EN ISO 9001 is made available
TVEDP1FL/100/G2/XSMB0-J6/M/200 – 900 [m³/h]
|||||||||
123456789

1 Type
TVE
VAV terminal unit

2 Acoustic cladding
No entry: without acoustic cladding
D With acoustic cladding

3 Material
No entry: galvanised sheet steel
P1 Air duct powder-coated RAL 7001 (silver grey)
A2 Stainless steel variant

4 Air duct connection
No entry: push-fit end for air ducts according to DIN EN 1506; with groove for optional seal
FL Flanges on both ends

5 Nominal size [mm]
100, 125, 160, 200, 250, 315, 400

6 Accessories
No entry: without accessories
D2 Double lip seal on both sides (only with push-fit end air duct connection)
G2 Matching flange for each flange (only with air duct connection FL)

7 Attachment (control component)
XSMB0-J6
Static volume flow controller with display, Modbus
RTU interface, RJ12 socket (for X-AIRCONTROL)

8 Operating state
M
Modbus RTU interface, variable operation (setpoint specification via Modbus register)

9 Operating values for factory setting
Volume flow rate [m³/h or l/s]
qᵥmin – qᵥmax

Order example: TVE/100/D2/XS0/M/20-350 m³/h

Acoustic claddingWithout
MaterialGalvanised sheet steel
Nominal size100 mm
AccessoriesDouble lip seal both sides
AttachmentCompact controller Modbus, static transducer
Operating modeModbus RTU
Volume flow rate20 – 350 m³/h

Compact controller for VAV terminal units

Part number

Type of installation component

VAV terminal units

A00000082306

TR0VM-024T-10I-DS12-BN

TVE, TVE-Q



Compact controller TR0VM-024T-10I-DS12-BN

Type of measurement/installation orientation

static measuring principle, position-independent

Supply voltage (AC)

24 V AC, ± 20 %, 50/60 Hz

Supply voltage (DC)

24 V DC ± 20 %


Power rating (AC)

TVE NW 100 - 160: maximum 4 VA

TVE NW 200 - 400: maximum 6 VA TVE-Q up to height 200: maximum 4 VA

TVE-Q from height 300: maximum 6 VA


Power rating (DC)

TVE-Q up to height 200: maximum 1.5 W TVE-Q from height 300: maximum 3 W TVE NW 100 – 160: maximum 1.5 W

TVE NW 200 - 400: maximum 3 W

Power consumption (when running/when idle)

1 W

Run time for 90°

100 s

Setpoint value signal input (analogue optional)

0 - 10 V DC, input resistance > 100 kΩ

or 2 - 10V DC Ra> 50 kΩ

Actual value signal output

0 - 10 V DC or 2 - 10 V DC; maximum 5 mA

IEC protection class

III (Protective extra-low voltage)

Protection level

IP 42 (with attached terminal cover)

EC conformity

EMC to 2014/30/EU

Bus connection

RS485, Modbus RTU

Number of nodes (bus participants)

128


adjustable communication parameters for Modbus

1200 – 115,200 Bd

Start bit: 1

Data bits: 8

Stop bits adjustable: 1 or 2

Parity adjustable: None, Even, Odd

Setpoint/actual value interface

via X-AIRCONTROL/Modbus register list

Cable termination

externally required (120 Ω)

Downloads

product information

production {"x-frame-options"=>"SAMEORIGIN", "x-xss-protection"=>"0", "x-content-type-options"=>"nosniff", "x-permitted-cross-domain-policies"=>"none", "referrer-policy"=>"strict-origin-when-cross-origin", "strict-transport-security"=>"max-age=31536000; includeSubDomains", "content-type"=>"text/html; charset=utf-8", "link"=>"</assets/application-efbc495b06ca980ef13dc743756002fce2f413f798fecb64c7f0c81954c16402.css>; rel=preload; as=style; nopush,</assets/print-fec2e47d6d8dcc5d4c101139f17046ba981ca1c12f71e7e403fba50cc7584175.css>; rel=preload; as=style; nopush,</assets/other_js/modernizr.custom.93544-c26374a79d804901074bb4aa6fd3fa44ea22e840389915d2adce16b024021ef3.js>; rel=preload; as=script; nopush,</assets/other_js/js.cookie.min-de103d86d1919b40950f791699b4ce768137fde41af09b35ff92bde369732183.js>; rel=preload; as=script; nopush,</assets/other_js/jquery-3.5.1-2c4ce18a1a3f144c333912efc24a76c9a165a0dba9f88a499985df1af0a196a2.js>; rel=preload; as=script; nopush"}

Share page

Recommend this page

Recommend this page by sending a link by mail.

Fields marked with an (*) are required fields.

Share page

Thank you for your recommendation!

Your recommendation has been sent and should arrive shortly.

Contact

We are here for you

Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

Attachment (max. 10MB)

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

Contact

We are here for you

Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

Attachment (max. 10MB)

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265