| 1 Outdoor air temperature sensor (optional) | 10 Bypass damper with actuator |
| 2 Shut-off damper with actuator (exhaust air and outdoor air) | 11 CO2 sensor (optional) |
| 3 Outdoor air filter | 12 Extract air filter |
| 4 Fan (supply air and extract air) | SEH Single room exhaust air |
| 5 Recuperative cross flow plate heat recovery | SET Single room extract air |
| 6 Sound attenuator | SRO Single room outdoor air |
| 7 Heating coil | SRS Single room supply air |
| 8 Cooling coil (only SCHOOLAIR-V-4) | SEC Secondary air (optional) |
| 9 Supply air temperature sensor |
Functional description
Decentralised supply and extract air units ventilate the room and cover the cooling and heating load in accordance with the technical data. An EC centrifugal fan takes in the outdoor air which then flows through the motorised shut-off damper and the outdoor air filter. The outdoor air then flows through the cross flow heat recovery unit, which can be switched off in energy efficient operating situations. Before the supply air flows into the room like displacement air, it is heated or cooled in the heat exchanger if required (optional for 4-pipe units).The extract air first passes through the extract air filter, then flows through the heat recovery unit, the extract air fan and the motorised shut-off damper before it is discharged to the outside as exhaust air. If the indoor air quality is sufficient, the FSL-CONTROL III control system switches to energy-efficient secondary air mode by closing the outdoor air dampers. The control system compares the room air quality setpoint value to the actual value measured by the CO2 sensor and switches automatically between outdoor air and secondary air operation. In case of a power failure, the outdoor air and exhaust air dampers are closed to ensure fire protection, frost protection and to avoid draughts. This is ensured by a capacitor in each actuator. Near the external wall, the supply air is discharged into the room with a medium velocity between 0.5 and 0.8 m/s. Due to the induction effect, the supply air velocity is rapidly reduced after entering the room. As a result, in cooling mode, the supply air spreads out like displacement flow over the entire floor area. Near heat sources such as people or equipment, a lift current is formed by natural convection, so that the air is exchanged primarily in these areas.
| Width | 397 mm |
| Height | 2350 mm |
| Depth | 359 mm |
| Volume flow rate | 150, 200, 250 m³/h (boost 320 m³/h) |
| Nominal volume flow rate | 250 m³/h |
| Sound power level | 31 – 46 dB(A) |
Heat recovery efficiency | 52 % |
| Maximum operating pressure, water side | 6 bar |
| Maximum operating temperature | 75 °C |
| Supply voltage | 230 V AC ±10 %, 50/60 Hz |
| Power rating | 226 VA |
| Weight | 85 kg |
| SA-V | – | – | 4 | – | 1 | – | KM | / | 397 × 2350 × 359 | / | C3 | – | MA | – | T | / | MR | / | C | / | Z | / | A | / | HV | – | R | – | 0,40 | / | KV | – | R | – | 0,40 | |
| | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | ||||||||||||||||||
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 15 | 16 | 17 | 18 | 19 |
Order example: SA-V-4-1-KM/397×2350×359/C3-MA-T/MR/C/Z/A/HV-R-0.40/KV-R-0.40
| Type | SA-V | Ventilation unit for ceiling installation X-CUBE/SCHOOLAIR-V |
| Variant | - | Standard |
| Heat exchanger | 4 | 4-pipe |
| Heat exchanger construction | 1 | Heat exchanger type 1 |
| Construction | KM | with condensate drain |
| Nominal size [mm] | 397×2350×359 | Width 397, height 2350, depth 359 |
| Control | C3 | with FSL-CONTROL III |
| Control function | MA | Master |
| Real time clock | T | with real time clock |
| Interface | MR | with Modbus RTU |
| Air quality sensor | C | with CO2sensor |
| Supply air temperature sensor | Z | with supply air temperature sensor |
| Outdoor air temperature sensor | A | with outdoor air temperature sensor |
| Heating valve | HV | with thermoelectric actuator |
| Lockshield – heating circuit | R | with lockshield |
| kVS value – heating valve | 0.40 | 0.40 (straight-way valve) |
| Cooling valve | KV | with thermoelectric actuator |
| Lockshield – cooling circuit | R | with lockshield |
| kVS value – cooling valve | 0.40 | 0.40 (straight-way valve) |
Share page
Recommend this page
Recommend this page by sending a link by mail.
Share page
Thank you for your recommendation!
Your recommendation has been sent and should arrive shortly.
Contact
We are here for you
Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
We are here for you
Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265