This specification text describes the general characteristics of the product. Texts for variants can be generated with our Easy Product Finder design programme.
Specification text
SA-V
Under sill ventilation units for vertical installation on the façade
TROX SCHOOLAIR-V under sill ventilation unit with supply and extract air function, heat recovery and switchover option to secondary air mode (depending on air quality) as well as heating and/or cooling function, for vertical installation on the façade:
- Device casing made of galvanised sheet steel
- Cover and sheet metal connections: Connection via deep-drawn threads and stainless steel cross-head screws
- All necessary internal air ducts sealed and insulated by lining
- Internal electrical cable glands sealed
- Visible surfaces powder-coated (RAL 9005, jet black)
- Sound and heat-insulating lining on the suction and discharge side:
- Glass fibre-laminated mineral wool (building material class A, non-combustible according to DIN 4102, T1), abrasion-resistant up to air velocities of 20 m/s, or closed-cell insulation material
- The device meets the hygiene requirements of VDI 6022
- Height-adjustable levelling feet, +40 mm, to compensate for structural tolerances
- Connection to the on-site outdoor air and exhaust air openings in the façade:
- With circumferential closed-cell sealing tape on the back of the device, 10 mm thick
- The intake and discharge resistance of the on-site construction should not exceed 20 Pa at nominal volume flow
- Room-side extract air intake at the top of the unit front
- Use of 2 energy-saving EC centrifugal fans:
- Supply and extract air fan classified in category SFP 0 (< 300 W/(m³/s)) in accordance with DIN EN 16798-3:2017-11
- Suitable for 4 speed levels:
- Control via the unit-integrated single-room control
- Volume flow rate correction possible after installation by adjusting the control voltage
- Technical requirements of EU Regulation 1253/2014 for non-residential ventilation systems:
- Compliant and documented in accordance with the regulation
- Motorised shut-off dampers in outdoor and exhaust air areas:
- Normally closed in inactive state due to capacitor
- Open-close actuator 230 V AC
- Control via the unit-integrated single-room control
- Automatic switchover to energy-efficient secondary air operation:
- Only in conjunction with air quality sensor
- Comparison of setpoints with the internal CO2 sensor readings
- If the indoor air quality is adequate: Automatic changeover from outdoor air mode to secondary air mode
- Connection point to the on-site electrical system:
- Cable for on-site connection (not included in TROX scope of supply)
- Cable (L, N, PE) with wire end ferrules, approx. 1 m exiting the device
- On-site electrical system: 1~ 230 V AC, 50 Hz, 3 x 1.5 mm2 (3-core)
- Electrical components in the device:
- Completely wired with FSL-CONTROL III control system
- Control components integrated in the device
- Connection option for bus communication (optional)
- Connection of room control panel etc. after opening the customer area of the control system
- Connection point to the on-site Measurement/Control/ Regulation technology: Rail-mounted terminals type Wago 260
- Master unit:
- Optional integration into MCE/BACS via RS485 (Modbus/BACnet)
- Master-slave connection RS485
- Digital outputs DO
- Digital inputs DI
- Room control panel for measuring room temperature
- Slave unit:
- Master-slave connection RS485
- Connection point to the on-site Measurement/Control/ Regulation technology: Network connection RJ45
- Optional integration into an on-site MCE/BACS via Ethernet (Modbus/BACnet)
- RJ45 connection socket as service access to the user interface
- Under-sill cladding, to be provided by the client:
- Must have perforations: for supply air intake, for extract air and secondary air intake
- Must not restrict maintenance work or installation and removal of the unit from the front
- Clear distance between the front edge of the unit to the inner edge of the under-sill cladding: approx. 30 mm
- Closed-cell sealing tapes for sealing and adapting to the on-site cladding: not included in the TROX supply package
- Filter change:
- Quick filter change
- Tool-free opening of the filter cover thanks to userfriendly quarter-turn fasteners (after opening the onsite cladding)
- Accessibility must not be restricted by the on-site sill cladding
Materials and surfaces0
Standard variant
- Fixing points for installation:
- Adjustable mounting bracket on top of the unit with 2 slotted holes
- 2 slotted holes in the rear wall of the casing, below the heat exchanger
- Power consumption and connection dimensioning
- Electrical power consumption of the entire unit at nominal volume flow 250 m³/h < 44 W
- For dimensioning the connecting cable: Take into account a connected load of 226 VA
- Integrated cross-flow heat recovery unit:
- Seawater-resistant aluminium design
- High efficiency: Heat recovery efficiency > 52 %
- Including condensate collection and drainage
- With electromotive bypass:
- Allows a partial airflow to bypass the heat recovery unit
- Actuator 24 V (modulating) 0 – 100 %
- Control via the unit-integrated single-room control
- Outdoor air filter as Mini Pleat filter class ePM1 (fine dust filter):
- Filter class according to ISO16890: ISO ePM1 65%
- Eurovent-certified
- Made from high-quality, wet-strength glass fibre paper
- In tight pleats
- Spacer:
- Made from thermoplastic hot-melt adhesive
- Even distance between the pleats (4 mm)
- Frame made of moisture-resistant nonwoven fabric with pull-out tabs
- The frame must not reduce the airflow cross-section (filter size = airflow cross-section)
- Filter area ≥ 2.96 m²
- Extract air filter (coarse dust filter) as flat filter medium, filter class according to ISO 16890: ISO Coarse 75 %
Sizing data
2
- 2-pipe aluminium copper tube heat exchanger for air heating:
- Adapted to the project-specific data
- Easily removable for cleaning (the on-site connection to the main pipework is crucial, not included in the TROX scope of delivery)
- Drain and vent option for each heating/cooling circuit
- Cleaning the heat exchanger:
- For easy removal: We recommend a connection to the on-site pipe network with flexible hoses (not included in the TROX scope of supply)
- Connection points are the heat exchanger connections, ½" flat-sealing with union nut
- Connection point to the on-site heating/plumbing system:
- Pre-assembled hand-tight control components
- Connection with external thread ½" flat-sealing
- In the return flow: Valve including actuator
- In the supply flow: Lockshield
KO
- Easy-to-clean condensate drip tray without condensate drain: made of galvanised sheet steel, powder-coated (RAL 9005)
KM
- Easy-to-clean condensate drip tray with condensate drain: Ø 12 x 1 mm made of galvanised sheet steel, powdercoated (RAL 9005)
Nominal size
- Width: approx. 397 mm
- Height: approx. 2160 mm (without levelling feet, without fixing bracket)
- Depth: approx. 359 mm (without façade seal)
C3
With FSL-CONTROL III:
- Single room controller for DIN rail mounting in the unit or in a separate control casing
- Integrated microSD card as flash memory medium
- At least 2 GB storage space
- Saves the trend data
- Accessible via RJ45 connection socket
- For simple master-slave communication via Modbus RTU
- Connection of up to 10 slave units to one master unit
- Software:
- 3 operating modes: Off, Automatic, Manual mode
- 3 operating states: Occupied, Unoccupied, Standby
- 4 operating state overrides: Boost, Class, night purge, fan forced circuit
- Basic distinction between room temperature control by controlling heating and cooling valves or modulating bypass damper, or supply air temperature control for isothermal ventilation operation
- Year-round heat recovery use
MA
Control function Master
- Software package specially developed for decentralised ventilation units
- Factory-equipped
- Configured for master units
- 42 digital or analogue inputs and outputs
- CO2-guided air quality control
- Alarm messages: Type A (shutdowns) and Type B (notifications)
SL
Control function Slave
- Software package specially developed for decentralised ventilation units
- Factory-equipped
- 28 digital or analogue inputs and outputs
T
Only with control function MA
Real-Time-Clock (RTC):
- Part of the master software package
- Includes a simple time programme
- 7 days with 10 switching points each
- Automatic switching between summer and winter time
- Night purge schedules
MTWith Modbus TCP
Modbus TCP interface (Ethernet):
- FSL-CONTROL III can be integrated into an on-site MCE/BACS via the Modbus TCP protocol.
- Required for visualisation via the X-TAIRMINAL
- Additionally including web server for simplified configuration, commissioning and remote monitoring of the device.
BI
With BACnet IP
BACnet IP interface (Ethernet):
- FSL-CONTROL III can be integrated into an on-site MCE/BACS via BACnet IP protocol.
- Additionally including web server for simplified configuration, commissioning and remote monitoring of the device.
MR
Only with control function MA
With Modbus RTU
Modbus RTU interface (RS 485):
- FSL-CONTROL III can be integrated into an on-site MCE/BACS via Modbus RTU
BM
Only with control function MA
With BACnet MS/TP
BACnet MS/TP interface (RS485):
- FSL-CONTROL III can be integrated into an on-site MCE/BACS via BACnet MS/TP
C
Only with control function MA
Air quality sensor
With CO2sensor:
- Component of the master unit
- Sensor located in the extract air intake to monitor indoor air quality and control the outdoor air volume flow accordingly.
- Measurement via an NDIR sensor that works on an infrared basis and compensates for any contamination through its 2-beam measuring principle
- Measuring range 0 – 2000 ppm
V
Only with control function MA
Air quality sensor
With VOC sensor
- Detection of a wide range of VOC emissions correlating with the CO2concentration in indoor air
- TVOC mit auto-calibration
- Detected indoor air substances include alcohols, aldehydes, aliphatic hydrocarbons, amines, aromatic hydrocarbons, CO, CH4, liquid gas, ketones, organic acids
- Detection range: 0 – 2000 ppm, VOC and CO2equivalent
- Self-test and automatic zero-point adjustment
Z
With supply air temperature sensor
- Supply air temperature sensor with NTC thermistor sensing element
- Resistance 10 kΩ at 25 °C
- Measuring range -35 – 105 °C
- Very short response time due to perforated measuring tip
A
With outside air temperature sensor (only with MA control function)
- Outdoor air temperature sensor with NTC thermistor sensing element
- Resistance 10 kΩ at 25 °C
- Measuring range -35 – 105 °C
HV
Thermoelectric valve actuator:
- For opening and closing valves
- With position indicator
- Including plug-in connecting cable
- Supply voltage: 24 V DC
- Control voltage 0 – 10 V DC
- Power consumption 1 W
- Protection rating: IP 54
HVE
Electromotive valve actuator
- For opening and closing valves
- Supply voltage 24 V AC/DC
- Power consumption max. 2.5 VA
- Control signal 3-point DC 0 – 10 V
- Permissible media temperature 1 – 110 °C
R
Lockshield
- For regulation and shut-off
- Valve casing: straight way
- External thread on both sides ½" flat sealing
- Hand-tightened pre-assembled
- Nominal width DN 15
- Maximum media temperature 120 °C
0.25
Straight-through small valve:
- Straight-through valve body
- Male thread on both sides ½" flat sealing
- Pre-assembled hand-tight
- PN 16
- DN 10
- Kvs value 0.25
- Media temperature 1 – 110 °C
0.40
Straight-through small valve:
- Straight-through valve body
- Male thread on both sides ½" flat sealing
- Pre-assembled hand-tight
- PN 16
- DN 10
- Kvs value 0.40
- Media temperature 1 – 110 °C
0.63
Straight-through small valve:
- Straight-through valve body
- Male thread on both sides ½" flat sealing
- Pre-assembled hand-tight
- PN 16
- DN 10
- Kvs value 0.63
- Media temperature 1 – 110 °C
1.00
Straight-through small valve:
- Straight-through valve body
- Male thread on both sides ½" flat sealing
- Pre-assembled hand-tight
- PN 16
- DN 10
- Kvs value 1.00
- Media temperature 1 – 110 °C
F0.50
Pressure-independent control valve
- Straight-through valve body
- Male thread on both sides ½" flat sealing
- Pre-assembled hand-tight
- With modulating Open-Close control in combination with an externally adjustable, dynamic volume flow controller
- With full valve authority
- Nominal width DN 10
- Media temperature 0 – 120 °C
Replacement filter set
- Extract air filter: Filter pad
- Outdoor air filter: Mini-Pleat-Filter
| SA-V | – | | – | 2 | – | 1 | – | KO | / | 397 × 2160 × 359 | / | C3 | – | MA | – | T | / | MR | / | C | / | Z | / | A | / | HV | – | R | – | 0,40 |
| | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
| 1 | | 2 | | 3 | | 4 | | 5 | | 6 | | 7 | | 8 | | 9 | | 10 | | 11 | | 12 | | 13 | | 14 | | 15 | | 16 |
1 Type
SA-V vertical decentralised ventilation unit X-CUBE/SCHOOLAIR-V
2 Variant
No entry: Standard
3 Heat exchanger
2 2-pipe
4 Heat exchanger construction
Specify construction (technical design with TROX EPF or TROX CONFIGURATOR)
5 Construction
KO without condensate drain
KM with condensate drain
6 Nominal size [mm]
Width x height x depth
397 x 2160 x 359
7 Control system
OR without control system
C3 with FSL-CONTROL III
8 Control function
MA Master
SL Slave
9 Real-time clock
Only with control function MA
No entry: without real time clock
T with real time clock
10 Interface
No entry: without interface
MT with Modbus TCP
MR with Modbus RTU (only with control function MA)
BI with BACnet IP
BM with BACnet MS/TP (only with control function MA)
11 Air quality sensor
Only with control function MA
No entry: without air quality sensor
C with CO2 sensor
V with VOC sensor
12 Supply air temperature sensor
Z with supply air temperature sensor
13 Outdoor air temperature sensor
Only with control function MA
No entry: without outdoor air temperature sensor
A with outdoor air temperature sensor
14 Heating valve
HV with thermoelectric actuator
HVE with electromotive actuator
15 Lockshield – heating circuit
R with lockshield
16 Kvs value heating valve
0.25 (straight-way valve)
0.40 (straight-way valve)
0.63 (straight-way valve)
1.00 (straight-way valve)
F0.50 (pressure-independent control valve)
Order example: SA-V-2-1-KO/397x2160x359/C3-MA-T/MR/C/Z/A/HV-R-0.40
| Type | SA-V | Ventilation unit for ceiling installation X-CUBE/SCHOOLAIR-V |
| Variant | - | Standard |
| Heat exchanger | 2 | 2-pipe |
| Heat exchanger construction | 1 | Heat exchanger type 1 |
| Construction | KO | without condensate drain |
| Nominal size [mm] | 397×2160×359 | Width 397, height 2160, depth 359 |
| Control system | C3 | with FSL-CONTROL III |
| Control function | MA | Master |
| Real time clock | T | with real time clock |
| Interface | MR | with Modbus RTU |
| Air quality sensor | C | with CO2 sensor |
| Supply air temperature sensor | Z | with supply air temperature sensor |
| Outdoor air temperature sensor | A | with outdoor air temperature sensor |
| Heating valve | HV | with thermoelectric actuator |
| Lockshield heating circuit | R | with lockshield |
| Kvs value heating valve | 0.40 | 0.40 (straight-way valve) |