For mechanical smoke extract systems, smoke control damper for individual sections

Rectangular sheet steel smoke control damper including ventilation function for the removal of smoke and heat in smoke extract systems, as well as for the controlled flow of the necessary supply air. Suitable as a support for keeping safety rooms and their anterooms smoke-free in pressurised ventilation systems (DBA), e.g., in fire brigade lift shafts or for smoke removal in escape tunnels.


  • Can be used in discharge environments with elevated temperatures of up to 600 °C at tested smoke extract ducts and sheet steel ducts
  • Meets pressure level 3 with any airflow direction and automatic release (AA)
  • Nominal sizes 100 × 100 – 1250 × 2560 mm
  • Volume flow rate of 360 m³/h or 100 l/s – 115110 m³/h or 31975 l/s at 10 m/s
  • Design in sheet steel (also powder-coated according to RAL-CLASSIC chart) or stainless steel sheet in A4 quality
  • According to EN 1751: Leakage air flow with closed damper at least class 2 and casing leakage air flow class B, from nominal sizes 840 × 480 leakage air flow with closed damper 3 and casing leakage air flow class C
  • Integration into the central BMS with TROXNETCOM or with interface modules such as those in SLC® technology
  • Cmod for smoke extraction with ventilation function and control characteristics in combined systems (combination damper) and therefore pneumatic balancing possible via travel to intermediate positions
Product successfully added to cart

General Information

Application

  • Smoke control damper with CE marking and declaration of performance for the dissipation of smoke and heat in smoke control systems with mechanical smoke control devices
  • Use in pressurised ventilation systems (DBA) with ventilation function, but also for outside air supply (afterflow) 
  • Integration into the central BMS with TROXNETCOM or other standard bus systems possible



Classification

E600 120 (ved hod i↔o) S 1500 Cmod AA Single




Nominal sizes

  • 100 × 100 to 1250 × 2560 mm
  • Casing length L = 200 mm



Parts and characteristics

  • For increased temperatures up to 600 °C
  • Permitted for automatic release AA 
  • Smoke control damper with ventilation function
  • Adjustable discharge and afterflow volumes
  • Pressure level 3 (operating pressure -1500/+500 Pa)



Attachments

  • Cover grille: Expanded metal mesh
  • OPEN/CLOSE actuators with 24 V AC/DC or 230 V AC supply voltage
  • Constantly regulating actuators with 24 V AC/DC
  • Network modules for integration with AS-i networks
  • Network modules for other standard bus systems, such as the required SLC® technology


Optional products



TROXNETCOM

  • X-FANS control unit for extract air and smoke extract control

 

TROX-X FANS smoke exhaust fans from the X-FANS subassembly

  • Smoke exhaust fan for roof installation BVDAX/BVD 
  • Smoke exhaust fan for wall installation BVW/BVWAXN 
  • Smoke exhaust centrifugal fan BVREH/BVRA 
  • Smoke exhaust jet fans BVGAX/BVGAXN

 

All smoke exhaust fans are tested to ​EN 12101-3, for F200/F300/​F400 and F600, depending on the type. With CE marking, declaration of performance and application approval for the German market. Speed adjustment for smoke exhaust fans

  • X-FANS control, certified frequency inverter unit
  • Safe and precise speed adjustment of smoke exhaust fans both in single-zone and in multi-zone systems.



Construction features



  • Rectangular construction
  • Opposite opening and closing of the damper blade field
  • The smoke control damper is driven by a reversible OPEN/CLOSED actuator or a continuously regulating actuator with 0 - 10 V control voltage
  • Suitable for the connection of cover grilles 
  • Suitable for front and rear connection of sheet steel cables



Materials and surfaces

  • Casing, damper blade, mechanics optionally galvanised steel or stainless steel in A4 quality
  • Surfaces can be finished in colours according to RAL chart
  • Bearings are DU-coated
  • Seals made of glass fabric and high-temperature sealing tape (HT sealing tape)



Standards and guidelines



  • Construction Products Regulation 
  • EN 12101-8 Smoke and heat control systems – Smoke control dampers
  • EN 1366-10 Fire resistance tests for service installations – Smoke control dampers
  • EN 13501-4 Fire classification of construction products and building elements using data from fire resistance tests
  • EN 1751 Ventilation for buildings – Air terminal devices



Maintenance



Smoke control dampers must be operational at all times and must be maintained regularly so that they meet the performance requirements.

  • Maintenance is required at least every 6 months
  • A maintenance report must be created; documents must be kept for reference
  • The functional reliability of the smoke control damper must be tested at least every six months; this has to be arranged by the owner of the smoke extract system; functional tests must be carried out in compliance with the basic maintenance principles stated in EN 13306 and DIN 31051. If two consecutive tests, one 6 months after the other, are successful, the next test of the smoke control damper can be conducted one year later.
  • Depending on where dampers are installed, country-specific regulations may apply.
  • For details on maintenance and inspection, refer to the installation and operating manual.


Technical information

Function, Technical data, Quick sizing, Specification text, Order code

  • Function
  • TECHNICAL DATA
  • QUICK SIZING
  • SPECIFICATION TEXT
  • ORDER CODE
Schematic illustration EK-JS_gc_05ai.png

1 Casing
2 Linkage cover (cut open)
3 Drive linkage
4 Actuator
5 Rating plate
6 Side seal
7 Damper blades
8 Damper blade profiled seal


Type EK-JS smoke control dampers are tested according to EN12101-8 and EN 1366-10. In rectangular steel and stainless steel construction. Intended for the discharge of smoke and heat in smoke extract systems and for the flow of necessary supply air into the area from which smoke is to be extracted. EK-JS is intended for use in pressurised ventilation systems (DBA) in order to keep safety stairwells and their anterooms and fire brigade lift shafts or escape tunnels smoke-free. They thus enable the controlled discharge of released smoke. EK-JS is intended for use in single sections and may be used at elevated operating temperatures of up to 600 °C on and in horizontally and vertically aligned smoke extract ducts according to EN 12101-7, tested according to EN 1366-9. EK-JS can be used in combined systems (combination damper) for ventilation and is suitable for restricting extract air volume flows. The OPEN-CLOSE actuators can be signalled either with ready-wired actuator control modules or with bus modules. 


Nominal sizes B × H

100 × 100 – 1250 × 2560 mm

Casing length

200 mm

Volume flow rate range at 10 m/s

From 360 m³/h to 115110 m³/h or
from 100 l/s to 31975 l/s

Differential pressure range

Pressure level 3: -1500 to 500 Pa

Operating temperature

30 °C – 50 °C without temperatures below the dew point

Upstream velocity with same upstream and downstream flow

  • ≤ 12 m/s
  • ≤ 20 m/s
    For dimensions, see motor allocation matrix (technical clarification with TROX required for some sizes)

Closed damper blade air leakage

EN 1751, at least class 2,
from nominal width 840 × 480 class 3

Casing leakage

EN 1751, class B, from nominal width 840 × 480 class C

EC conformity



  • EU Construction Products Regulation No. 305/2011
  • EN 12101-8: Smoke and heat control systems – Part 8: Smoke control dampers
  • EN 1366-10: Fire resistance tests for service installations – Part 10: Smoke control dampers
  • EN 13501-4: Fire classification of construction products and building elements – Part 4: Fire resistance tests on components of smoke control
  • EN 1751: Ventilation for buildings – Air terminal devices

Declaration of performance

DoP/EK-JS/001

,



  • Quick sizing tables in the Easy Product Finder provide a good overview of the volume flow rates for different airflow velocities and the corresponding differential pressures
  • Exact values can be determined with the help of our design program EPF
  • You will find the Easy Product Finder on our website: 
    www.trox.de/mytrox/auslegungsprogramm-easy-poduct-finder-182e16348fac3d33


Correction for different throttle positions

The adjustment of the damper blade angle enables the setting of different throttle positions.
Based on the determined data for the open position, both the resistance coefficient and the sound power level can be corrected to design the operating conditions with angled blades.
For this purpose, the resistance coefficient is multiplied by the correction factor C, which corresponds to the diagram of the "Resistance factor"
for the correction factor.
For the correction of the sound power level, this is added to the correction value K, which corresponds to the diagram of the "Sound power level"
for the correction value.
Smoke control dampers with a height of less than or greater than 320 mm are differentiated.

 

Example:
EK-JS / installation case A 
H × B: 960 mm × 1000 mm
Upstream velocity: 5 m/s


EPF (data for OPEN position)

  • Resistance factor = 0.23
  • Sound power level = 40 dB(A)

 

Correction for a blade angle of 65
(read from diagram correction factor "resistance coefficient" and correction value "sound power level")

 

Resistance factor:
Correction value C = 20
0.23 × 20 = 4.6

 

Sound power level:
Correction value K = 8
40 dB(A) + 8 dB(A) = 48 dB(A)

Type EK-JS smoke control dampers are tested according to EN12101-8 and EN 1366-10. In rectangular steel and stainless steel construction. Intended for the discharge of smoke and heat in smoke extract systems and for the flow of necessary supply air into the area from which smoke is to be extracted. EK-JS is intended for use in pressurised ventilation systems (DBA) in order to keep safety stairwells and their anterooms and fire brigade lift shafts or escape tunnels smoke-free. They thus enable the controlled discharge of released smoke. EK-JS is intended for use in single sections and may be used at elevated operating temperatures of up to 600 °C on and in horizontally and vertically aligned smoke extract ducts according to EN 12101-7, tested according to EN 1366-9. EK-JS can be used in combined systems (combination damper) for ventilation and is suitable for restricting extract air volume flows. The OPEN-CLOSE actuators can be signalled either with ready-wired actuator control modules or with bus modules. 


Materials and surfaces


  • Casing, damper blades and mechanics: optionally galvanised steel or stainless steel
  • Optional powder-coated casing and damper blades in standard RAL colour 7030 or according to RAL chart
  • Plain bearing: Coated steel
  • Grille attachment: Galvanised sheet steel, powder-coated
  • Seals made of glass fabric and high-temperature sealing tape  


Technical data


Exemplary for a nominal smoke control damper width of 1250 × 960 related to the mean airflow velocities v = 5 m/s

∆Pt = 3.5 Pa

dB(A) = 40

Afree  = 1.095 m²

Ageo = 1.2 m²

qv = 21600 m³/h




Standards and guidelines

  • Product standard EN 12101-8
  • Classification according to EN 13501-4 
  • Tested according to EN 1366-10 (for pressure level 3: up to 1500 Pa negative pressure)
  • Determination of air leakage with closed damper field according to EN 1751, at least class 2, from nominal width 840 × 480 class 3
  • Casing leakage to EN 1751, class B, from nominal width 840 × 480 class C



Classification

E600 120 (ved hod i↔o) S 1500 Cmod AA Single




Nominal sizes

Dimensions B × H: 100 × 100 – 1250 × 2560 [mm]

Casing length L = 200 mm 




Accessories

  • HT sealing tape
  • Suspension bracket for horizontal damper alignment



Attachments

  • Cover grille: Expanded metal mesh
  • OPEN/CLOSE actuators with 24 V AC/DC or 230 V AC supply voltage
  • Constantly regulating actuators with 24 V AC/DC
  • Network modules for integration with AS-i networks
  • Network modules for other standard bus systems, such as the required SLC® technology


Equivalence criteria

  • Large discharge openings up to 3.2 m² with only one actuator
  • For increased temperatures up to 600 °C
  • Operating pressure -1500/+500 Pa (pressure level 3)
  • Cmod for the smoke extract and ventilation function with control characteristics across all nominal sizes, control range 30 - 90° damper blade position
  • Automatic release (AA) also with TROXNETCOM or network modules for other standard bus systems, for e.g., required SLC® technology
  • Any upstream airflow direction
  • In galvanised construction with or without powder coating and in stainless steel construction

EK-JS2 / DE / 600 × 800 / 17 / K0 / B24A / P1 – RAL... / P2 – RAL...
|||||||||
123456789

1 Type
EK-JS
Smoke control damper according to EN 12101-8 2 ConstructionNo entry required: Galvanised steel standard construction

2 Stainless steel 


3 Country of destination
DE Germany
CH Switzerland

AT Austria

PL Poland
and others

4 Nominal size [mm]Width between 100 – 1250 mm in 5 mm steps in combination with height 100, 125, 150 or 165 mm.Width between 180 – 1250 mm in 5 mm steps in combination with height 320 to 2560 mm in 160 mm steps.

5 Accessories
No entry required: None (standard)
17 HT sealing tape (15 mm)
18 Suspension brackets for horizontal damper alignment
19 Suspension brackets for horizontal damper alignment and HT sealing tape (15 mm)

6 Attachments 1
No entry required: None (standard) 
Expanded metal mesh 14 × 16, galvanised steel
Without attachment on operating/installation side

First character signifies operating side (
0, K)
Second character signifies installation side (0, K)Any combination is possible

7 Attachments
2
24 V AC/DC:
B24 (Actuator)
B24SR (Actuator continuous control, ventilation function Cmod1) 24 V AC/DC: with operating range DC 2 – 10 V230 V AC:

B230 (Actuator)

Actuator combined with TROX control module:Module for signalling, TROXNETCOM:
B24A  (B24 actuator + TROXNETCOM control module AS-EM/EK2)
B24AS (B24 actuator + TROXNETCOM control module AS-EM/SIL22)
B24AM (B24 actuator + TROXNETCOM control module AS-EM/M, for function Cmod1)
Other communication modules:Belimo: Communication and power supply unit
B24BKNE (B24 actuator + BKNE230-24)
 
BV-Control: Communication and power supply unit with SLC®technology:
B24C (B24 actuator + BC24 G2)Agnosys: BRM-10-F fire damper and smoke control damper module
B24D (B24 actuator + BRM-10-F-ST)
B230D (B230 actuator + BRM-10-F) 

1
Function Cmod For damper blade in intermediate position
2 The AS-i system is based on the industrial standard AS-Interface

8 Standard construction of surface

No entry required: None (standard)

P1 Powder-coated RAL 7030 (technical lacquer paint finish), industrial polyester
80% ±5 gloss levels, texture grade: texturedor all other colours according to RAL chart, gloss level
80% ± 5 gloss levels, texture grade: smooth 

9 Surface of attachment 1
No entry required: None (standard)

P2 Powder-coated RAL 7030 (technical lacquer paint finish), industrial polyester
80% ±5 gloss levels, texture grade: texturedor all other colours according to RAL chart, gloss level
80% ± 5 gloss levels, texture grade: smooth


Order example: EK-JS/DE/600×800/17/K0/B24A/P1-RAL9010-80%-glatt
TypeEK-JS
Construction        Galvanised steel standard construction
Country of destinationGermany
Nominal size600 × 800
AccessoriesHT sealing tape
Attachment 1Expanded metal mesh on the operating side
Attachment 2Actuator with TROXNETCOM control module AS-EM/EK
Standard construction of surfaceP1 RAL 9010 80%: Smoke control damper with powder coating,
RAL 9010, pure white, gloss level 80%, texture grade: smooth
Surface of attachment 1None (standard)

Dimensions

  • DIMENSIONS

⓵ Keep area free for accessibility of the actuator
② Fixing option for control module

Weights [kg], width 100 – 650 mm

HB
100150200250300350400450500550600650
1007.337.658.028.338.658.979.289.69.9210.2310.5510.87
1257.587.98.278.598.99.229.549.8610.1810.510.8211.14
1507.828.158.528.849.169.489.810.1310.4510.7711.0911.41
1658.078.398.779.099.429.7410.0610.3910.7111.0411.3611.69
32011.2911.9512.6213.2913.9514.6215.2815.9516.6217.29
48013.4114.1714.9215.6816.4417.217.9518.7119.4720.22
64015.5416.3817.2318.0818.9219.7720.6221.4722.3123.16
80017.6618.619.5320.4721.4122.3523.2824.2225.1626.1
96019.7820.8121.8422.8723.924.9225.9526.9828.0129.04
112021.9623.124.2325.3726.5127.6428.7829.9231.0532.19
128024.1425.3826.6327.8729.1230.3631.6132.8534.135.35
144026.3127.6729.0230.3731.7333.0834.4335.7937.1538.72
160028.4929.9531.4132.8834.3435.837.4838.9540.4141.88
176030.6632.2433.8135.3837.1738.7440.3141.8843.4645.03
192032.8434.5236.4238.139.7841.4643.1444.8246.548.19
208035.0237.0338.8140.642.3944.1845.9747.7649.5551.34
224037.4139.3141.2143.14546.948.850.752.654.5
240039.5941.643.645.6147.6249.6251.6353.6355.6459.25
256041.7643.8845.9948.1150.2352.3454.4556.5760.2962.41


Weights [kg]. width 700-1250 mm

HB
700750800850900950100010501100115012001250
10011.1811.511.8212.1312.4512.7713.0813.413.7214.0314.3514.67
12511.4611.7812.112.4212.7313.0513.3713.6914.0114.3314.6514.97
15011.7312.0612.3812.713.0213.3413.6613.9914.3114.6314.9515.27
16512.0112.3312.6612.9813.3113.6313.9514.2814.614.9315.2515.58
32017.9518.6219.2819.9520.6221.2821.9522.6223.2823.9524.6225.29
48020.9821.7422.4923.2524.0124.7625.5226.2827.0327.7928.5529.31
64024.0124.8525.726.5527.3928.2429.0929.9430.7831.6332.4833.33
80027.0327.9728.9129.8530.7831.7232.6633.634.5335.4736.4137.35
96030.0631.0932.1233.1534.1735.236.2337.2638.2839.3140.3441.59
112033.3234.4635.636.7437.8739.0140.3741.542.6443.7744.9146.11
128036.5937.8339.340.5541.7943.0444.2845.5346.7748.0249.2650.51
144040.0741.4342.7844.1445.4946.8448.249.5550.952.2653.6255.03
160043.3444.846.2647.7349.1950.6552.1253.5855.0456.557.9759.43
176046.648.1749.7451.3252.8954.4656.0357.6159.1762.3563.9265.55
192049.8651.5553.2354.9156.5858.2761.5563.2364.9166.5968.2769.95
208053.1354.9256.7158.561.8863.6865.4767.2669.0470.8372.6274.47
224056.3959.8961.7963.6965.5867.4869.3871.2873.1875.0876.9878.88
240061.2563.2665.2767.2869.2871.2973.375.3177.3179.3281.3383.4
256064.5266.6468.7570.8772.9875.177.2279.3381.4483.5685.6887.8

Attachments

  • ATTACHMENTS


Application


  • Open/close actuators for the opening and closure of smoke control dampers, with automatic (AA) or manual release (MA).
  • With integral limit switches for capturing the end positions
  • Override control for up to 25 minutes
  • Ambient temperature for normal operation: -30 to 50 °C, up to 95%, without temperatures below the dew point, no condensation (EN 60730-1)
  • Two integral limit switches with volt-free contacts can indicate the damper blade position (OPEN and CLOSED)
  • The connecting cables of the 24 V actuator are fitted with plugs, which ensure quick and easy connection to the TROX AS-i bus system
  • The connecting cable of the 230 V AC actuator is fitted with wire end ferrules

 


Variants


B24


  • 24 V AC/DC supply voltage
  • BEN24-ST TR: Torque 15 Nm
  • BEE24-ST TR: Torque 25 Nm
  • BE24-12-ST TR: Torque 40 Nm
     

B230


  • Supply voltage 230 V AC
  • BEN230 TR: Torque 15 Nm
  • BEE230 TR: Torque 25 Nm
  • BE230-12 TR: Torque 40 Nm
     

B24-SR


  • BEN24-SR: Torque 15 Nm
  • BEE24-SR: Torque 25 Nm
     

The torque required to operate the smoke control damper depends on the size, which is why the actuator type cannot be chosen freely.

Torque tables


Wiring examples, technical data


ActuatorBEN24-STBEE24-STBE24-ST
Supply voltage (AC)AC 19.2 – 28.8 V, 50/60 Hz
Supply voltage (DC)DC 21.6 – 28.8 V, 50/60 Hz

Power consumption – when running

3 W2.5 W

12 W

Power consumption – when idle

0.1 W

0.5 W

Power rating for cable sizing

Imax. 8.2 A at 5 ms
Torque15 Nm25 Nm

40 Nm

Run time for 90°

< 30 s

Limit switch contacts

2 × EPU
Switching current1 mA – 3 A (0.5 A inductive), AC 250 V1 mA – 6 A (0.5 A inductive), AC 250 V
Limit switch – open
Limit switch – close80°87°
Connecting cable – actuatorCable 1 m, 3 × 0.75 mm², halogen-free

Connecting cable – limit switches

Cable 1 m, 6 × 0.75 mm², halogen-free
IEC protection classIII safety extra low voltage (SELV)
Protection level

IP 54

EC conformityCE according to 2014/30/EU
Low Voltage Directive CE according to 2014/35/EU
Operating temperature-30 to 55 °C
Weight0.9 kg1.1 kg

2.7 kg

ActuatorBEN230 TRBEE230 TRBE230 TR
Supply voltage (AC)AC 198 – 264 V, 50/60 Hz

Power consumption – when running

4 W3.5 W

8 W

Power consumption – when idle

0.4 W0.5 W

Power rating for cable sizing

Imax. 4 A at 5 msImax. 7.9 A at 5 ms
Torque15 Nm25 Nm

40 Nm

Run time for 90°

< 30 s

Limit switch contacts

2 × EPU
Switching current1 mA – 3 A (0.5 A inductive), AC 250 V1 mA – 6 A (0.5 A inductive), AC 250 V
Limit switch – open
Limit switch – close80°87°
Connecting cable – actuatorCable 1 m, 3 × 0.75 mm², halogen-free

Connecting cable – limit switches

Cable 1 m, 6 × 0.75 mm², halogen-free
IEC protection classII reinforced insulation
Protection level

IP 54

EC conformityCE according to 2014/30/EU
Low Voltage Directive CE according to 2014/35/EU
Operating temperature-30 to 55 °C-30 to 50 °C
Weight0.9 kg1.1 kg

2.7 kg

ActuatorBEN24-SRBEE24-SR
Supply voltage (AC)AC 19.2 – 28.8 V, 50/60 Hz
Supply voltage (DC)DC 21.6 – 28.8 V, 50/60 Hz

Power consumption – when running

3 W

Power consumption – when idle

0.3 W

Power rating for cable sizing

Imax. 8.2 A at 5 ms
Torque15 Nm25 Nm
Run time for 90°

< 30 s

Limit switch contacts

2 × EPU
Switching current1 mA – 3 A (0.5 A inductive), AC 250 V
Limit switch – open
Limit switch – close80°
Connecting cable – actuatorCable 1 m, 4 × 0.75 mm², halogen-free

Connecting cable – limit switches

Cable 1 m, 6 × 0.75 mm², halogen-free
IEC protection classIII safety extra low voltage (SELV)
Protection level

IP 54

EC conformityCE according to 2014/30/EU
Low Voltage Directive CE according to 2014/35/EU
Operating temperature-30 to 55 °C
Weight1.1 kg0.9 kg


Interfaces to higher level systems


TROX fire and smoke protection systems have standardised interfaces for central building management systems. In the simplest case, the interface consists of discrete signalling contacts that connect the alternating inputs and outputs of TROX systems and other building components.


Control and communication modules for smoke control dampers


TypeB24AB24ASB24BKNEB24CB230DB24DB24AM

AS-EM/EK

AS-EM/SIL2

BKNE230-24

BC24-G2

BRM-10-FBRM-10-F-STAS-EM/M
EK-EU

×

×

×

×

×

×

×

EK-JZ

×

×

×

×

×

×

×

EK-JS

×

×

×

×

×

×

×



Note:
Actuators and communication modules are factory tested together; only tested combinations must be used.


B24A – AS-EM/EK


Application


  • Module for the control of smoke control dampers
  • Capturing damper blade positions OPEN and CLOSED
  • Actuators can be started even without controller communication
  • LEDs for OPEN and CLOSED positions; monitoring of run time errors
  • Integral AS-Interface slave
  • Monitoring of signal reception
  • Master can be used to monitor the run time of the damper blade actuator
  • Supply voltage of the module and the 24 V DC actuator using AS-Interface ( 2-wire control)
  • Plug-in connection for Belimo actuators (factory-mounted and wired)


Use


B24A – Mounted to the smoke control damper

Description

AS-EM/EK

Electrical design

4 inputs/3 outputs

Output function

PNP transistor

Supply voltage

26.5 – 31.6 V DC

Current consumption, including actuator

450 mA



Inputs:


Switching

DC PNP

Sensor voltage supply

AS-i

Voltage range

18 – 30 V AC

With short circuit protection

Yes

Switching level – high signal 1

10

Input current high/low

> 7 mA/< 2 mA

Input characteristic

IEC 61131-2 Type 2



Outputs, PNP:


Galvanically isolated

No

Max. current load per output

400 mA per output/400 in total (from AS-i)


Outputs, relay:


Galvanically isolated

Yes

Maximum voltage

32 V

Max. current load

500 mA

Ambient temperature

-5 to 75 °C

Protection level, IEC protection class

IP 42

AS-i profile

S-7.A.E

I/O configuration

7 Hex

ID code

7 Hex

EMC

EN 61000-6-2; EN 61000-6-3

B24AS – AS-EM/SIL2


Application


  • Module for the control of smoke control dampers
  • Capturing damper blade positions OPEN and CLOSED
  • Approved up to SIL2 to IEC/EN 61508
  • Integrated AS-Interface
  • Monitoring of signal reception
  • Master can be used to monitor the run time of the damper blade actuator
  • Connection with terminals
  • Supply voltage of the module and the 24 V DC actuator using AS-Interface (2-wire control)
  • Plug-in connection for Belimo actuators (factory-mounted and wired)


Use


B24AS – Mounted to the smoke control damper

Description

AS-EM/SIL2

Supply voltage

26.5 – 31.6 V DC

Current consumption

< 400 mA from AS-i

Max. current load per output

340 mA

Max. current load per module

340 mA

Status LED

AS-i power

1 × green

PeripheralFault

1 × red, blinking

ComError

1 × red, static

Output Q0

1 × yellow (DO0)

Output Q1

1 × yellow (DO1)

Input status LED SI-1

1 × yellow

Input status LED SI-2

1 × yellow

Input status DI0

1 × yellow (DI0)

Input status DI1

1 × yellow (DI1)

Input status DI2

1 × yellow (DI2)

Binary inputs

2 outputs with transistor (typically 24 V DC from AS-i, voltage range 18 – 30 V)

Operating temperature

-20 to 70 °C

Storage temperature

-20 to 75 °C

Protection level, IEC protection class

IP 54

Casing material

Plastic

AS-i profile

S-7.B.E (Safety at Work) and S7.A.E (motor module)

EMC

EN 61000-6-2; EN 61000-6-3

B24AM – AS-EM/M



Application


  • Module for the control of smoke control dampers with Cmod function:
  • Capturing the damper blade end positions (CLOSED and OPEN)
  • Time-controlled selection of 13 intermediate positions of the damper blade (opening angle between 0° and 90°) 
  • Actuators can be started even without controller communication
  • Emergency position can be set (OPEN or CLOSED)
  • LEDs for OPEN and CLOSED positions; monitoring of run time errors
  • Integral AS-Interface slave
  • Monitoring of signal reception
  • Master can be used to monitor the run time of the damper blade actuator 
  • Supply voltage of the module and 24 V DC actuator using AS-Interface (2-wire control)
  • Plug-in connection for Belimo actuators


Use


B24AM – Mounted to the smoke control damper

DescriptionAS-EM/M

Electrical design

4 inputs/3 outputs

Output function

PNP transistor

Supply voltage

26.5 – 31.6 V DC

Current consumption, including actuator

450 mA

Inputs

Switching

DC PNP

Sensor voltage supply

AS-i

Voltage range

18 – 30 V AC

With short circuit protection

Yes

Switching level – high signal 1

10

Input current high/low

> 7 mA/< 2 mA

Input characteristic

IEC 61131-2 Type 2

Outputs, PNP

Galvanically isolated

No

Max. current load per output

400 mA per output/400 in total (from AS-i)

Outputs, relay

Galvanically isolated

Yes

Maximum voltage

32 V

Max. current load

500 mA

Ambient temperature

-5 to 75 °C

Protection level, IEC protection class

IP 42

AS-i profile

S-7.A.E

I/O configuration

7 Hex

ID code

7 Hex

EMC

EN 61000-6-2; EN 61000-6-3



B24BKNE – Communication module


Application

  • Communication and power supply unit for 24 V actuators in smoke extract applications, status LEDs, retention of the damper control input signal, 230 V AC connection, 1 m cable, free of halogens


Use

B24BKNE – BKNE230-24 communication module


DescriptionBKNE230-24

Nominal voltage

230 V AC 50/60 Hz

Functional range

198 – 264 V AC

Rating

19 VA (including actuator)

Power consumption

10 W (including actuator)

Length / cross section

On the actuator = 1 m, 3 (6*) × 0.75 mm² (free of halogens)

IEC protection class

II (protective insulation)

Ambient temperature

-30 to 50 °C

Storage temperature

-40 to 80 °C

Protection level

IP 54

EC conformity

EMC to 89/336/EEC, 73/23/EEC

Mode of action

Type 1 (EN60730-1)

Software class

A (EN60730-1)

Maintenance

Maintenance-free

Weight

680 g


B24C – Communication module



Application


  • SLC® technology
  • The BC 24 module is used for the control of damper actuators
  • Power supply and communication are implemented with an interchangeable two-core cable, SLC24-16B system.
  • A thermoelectric release mechanism and a duct smoke detector can be connected without the need for additional devices


Use


B24C – BC24-G2 communication module from BV-Control AG

DescriptionB24C

Nominal voltage

From SLC® control module

Power consumption

1 W

Connections

Plug connections, screw terminals

Damper power supply

24 V

Ambient temperature

-20 to 50 °C

Storage temperature

-20 to 80 °C

Humidity

95 % rh, no condensation

Weight

255 g

B × H × T

114 × 153 × 54 mm

Max. impulse voltage

2.5 kV (EN60730-1)


B24D, B230D – Communication module


Application

  • AGNOSYS system
  • BRM-F-ST module is used for the monitoring and control of smoke control dampers 
  • Up to 126 modules can be connected in a ring topology


Use

B24D – AGNOSYS BRM10FST communication module
B230D – AGNOSYS BRM10F communication module

DescriptionB24D/B230D

Nominal voltage

18 – 32 V DC (typically 24 V)

Connections

Plug connections, screw terminals

Damper power supply

24/230 V AC 24 V DC

Ambient temperature

0 to 45 °C

Humidity

90 % rh, no condensation

Weight

510 g

B × H × T

158 × 180 × 65 mm

Downloads

product information

certificates

operation manuals

production {"X-Frame-Options"=>"SAMEORIGIN", "X-XSS-Protection"=>"1; mode=block", "X-Content-Type-Options"=>"nosniff", "X-Download-Options"=>"noopen", "X-Permitted-Cross-Domain-Policies"=>"none", "Referrer-Policy"=>"strict-origin-when-cross-origin", "Content-Security-Policy"=>"frame-ancestors 'self' https://*.scrivito.com https://punchoutcommerce.com https://www.trox.de https://trox-extern.com https://*.onventis.com http://localhost:63342 http://cerebrum.local", "Strict-Transport-Security"=>"max-age=31536000; includeSubDomains", "Content-Type"=>"text/html; charset=utf-8"}

Share page

Recommend this page

Recommend this page by sending a link by mail.

Fields marked with an (*) are required fields.

Share page

Thank you for your recommendation!

Your recommendation has been sent and should arrive shortly.

Contact

We are here for you

Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

Contact

We are here for you

Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

Attachment (max. 10MB)

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265