SCHOOLAIR-B-HV-2/KM/2100x740x403/C3
Under sill units for assembly horizontally on the facade
Please note:
The described under sill ventilation unit variant is equipped with a single room control system arranged in the unit for autonomous classroom operation. The supplied controllers contain the standard control parameters for operation according to our control description
School ventilation unit – under sill installation – master unit
Under sill ventilation unit TROX SCHOOLAIR-B-HV with supply and extract air function, rotary heat recovery unit and switchover option to secondary air operation (air quality dependent) as well as heating function for installation on an external wall below the window sill:
Units – dimensions and weights:
Width: approx. 2100 mm (without fixing straps)
Height: approx. 740 mm (without levelling feet area, additional distance for exhaust air suction)
Depth: approx. 403 mm (without façade sealing)
Weight: approx. 150 kg
SEH Single room exhaust air
SET Single room extract air
SRO Single room fresh air
SRS Single room supply air
SEC Secondary air (optional)
1 Outdoor air temperature sensor (optional)
2 Shut-off damper with actuator (exhaust air and outdoor air)
3 Fresh air filter ISO ePM1 65 %
4 Sound attenuator
5 Fan (supply air and extract air)
6 Rotary heat exchanger for heat recovery
7 Heating coil
8 Cooling coil (optional)
9 Supply air temperature sensor
10 C02 sensor (optional)
11 Extract air filter ISO coarse 50 %
Decentralised supply and extract air units for room ventilation and for dissipating cooling loads and heat loads.
An EC centrifugal fan takes in the fresh air which then flows through the motorised shut-off damper and the fresh air filter.
The fresh air then flows through the rotary heat exchanger, which can be switched off when it is sensible with regard to energy efficiency.
If necessary, the air is heated or cooled by the heat exchanger before it is discharged to the room as a displacement flow (for 4-pipe systems this is optional).
The extract air first passes through the fresh air filter, then flows through the heat recovery unit, the extract air fan and the motorised shut-off damper before it is discharged to the outside as exhaust air.
If the room air quality is sufficient, FSL-CONTROL III closes the outdoor air dampers and changes to secondary air operation, which is more energy efficient in any case.
Here, the control unit compares the target values of the indoor air quality with the actual values measured at the CO2sensor and switches automatically between fresh air and secondary air operation.
If the power fails, the fresh air and exhaust air dampers are closed to ensure fire protection and frost protection and to avoid draughts. This is ensured by a capacitor in each actuator.
The supply air is discharged near the external wall and with a medium velocity between 1.0 and 1.5 m/s. Due to the induction effect, the supply air velocity is rapidly reduced so that, in cooling mode, the supply air is discharged as a displacement flow over the entire floor area.
The convection from people and other heat sources causes the fresh air from the pool to rise and create comfortable conditions in the occupied zone.
Width | 2100 mm |
Height | 740 mm |
Depth | 403 mm |
Volume flow rate | 200, 300, 400 m³/h (boost 600 m³/h) |
Nominal volume flow rate | 200, 300, 400 m³/h (boost 600 m³/h) |
Sound power level | 31 – 49 dB(A) |
Heat recovery efficiency | 75% |
Max. operating pressure, water side | 6 bar |
Max. operating temperature | 75 °C |
Supply voltage | 230 V AC ±10 %, 50/60 Hz |
Power rating | 617 VA |
Weight | 150 kg |
SCHOOLAIR-B-HV (example 2-pipe construction - active heating)
Supply air flow rate | m³/h | 200 | 300 | 400 | 600 |
Total heating capacity | W | 1780 | 2530 | 3150 | 4120 |
Room heating capacity | W | 1156 | 1603 | 1910 | 2285 |
Air temperature inside the unit | °C | 13.5 | 13.5 | 13.5 | 13.5 |
Supply air temperature | °C | 39.3 | 38.0 | 36.3 | 33.4 |
Hot water flow rate | l/h | 70 | 110 | 140 | 180 |
Water temperature, inlet | °C | 60 | 60 | 60 | 60 |
Water temperature, outlet | °C | 37.9 | 40.0 | 40.5 | 40.1 |
Water side pressure drop | kPa | 1.5 | 3.5 | 5.5 | 8.5 |
Sound power level LWA | dB(A) | 31 | 37 | 42 | 49 |
Sound pressure level with 8 dB system attenuation | dB(A) | 23 | 29 | 34 | 41 |
Active power Pe,l | W | 40 | 65 | 105 | 205 |
SCHOOLAIR-B-HV (example 2-pipe construction - isothermal supply air)
Supply air flow rate | m³/h | 200 | 300 | 400 | 600 |
Total heating capacity | W | 686 | 1055 | 1489 | 2111 |
Room heating capacity | W | 47 | 90 | 200 | 180 |
Air temperature inside the unit | °C | 11.8 | 11.8 | 11.8 | 11.8 |
Supply air temperature | °C | 21.7 | 21.9 | 22.5 | 21.9 |
Hot water flow rate | l/h | 20 | 33 | 50 | 80 |
Water temperature, inlet | °C | 60 | 60 | 60 | 60 |
Water temperature, outlet | °C | 30.3 | 32.4 | 34.2 | 37.2 |
Water side pressure drop | kPa | 1 | 1.5 | 3.5 | 7 |
Sound power level LWA | dB(A) | 31 | 37 | 42 | 49 |
Sound pressure level with 8 dB system attenuation | dB(A) | 23 | 29 | 34 | 41 |
Active power Pe,l | dB(A) | 40 | 65 | 105 | 205 |
SCHOOLAIR-B-HV (example 4-pipe construction)
Supply air flow rate | m³/h | 200 | 300 | 400 | 600 |
Total cooling capacity | W | 630 | 950 | 1190 | 1550 |
Room cooling capacity | W | 534 | 802 | 1002 | 1303 |
Air temperature inside the unit | °C | 27.5 | 27.5 | 27.5 | 27.5 |
Relative humidity | % | 52 | 52 | 52 | 52 |
Water content of the dry air | kg | 11.9 | 11.9 | 11.9 | 11.9 |
Supply air temperature | °C | 18 | 18 | 18.5 | 19.5 |
Condensation | g/h | 0 | 0 | 0 | 0 |
Chilled water flow rate | l/h | 100 | 140 | 160 | 180 |
Water temperature, inlet | °C | 16 | 16 | 16 | 16 |
Water temperature, outlet | °C | 21.5 | 21.5 | 22.0 | 23.5 |
Water side pressure drop | kPa | 9 | 16 | 20 | 25 |
Total heating capacity | W | 1680 | 2500 | 3260 | 4150 |
Room heating capacity | W | 635 | 902 | 1202 | 1102 |
Air temperature inside the unit | °C | 7.6 | 7.6 | 7.6 | 7.6 |
Supply air temperature | °C | 31.5 | 31.0 | 31.0 | 27.5 |
Hot water flow rate | l/h | 40 | 65 | 95 | 115 |
Water temperature, inlet | °C | 60 | 60 | 60 | 60 |
Water temperature, outlet | °C | 32.0 | 28.0 | 31.0 | 29.0 |
Water side pressure drop | kPa | 4 | 10 | 20 | 25 |
Sound power level LWA | dB(A) | 31 | 37 | 42 | 49 |
Sound pressure level with 8 dB system attenuation | dB(A) | 23 | 29 | 34 | 41 |
Active power Pe,l | W | 40 | 65 | 105 | 205 |
SCHOOLAIR-B-HV-2/KM/2100x740x403/C3
Under sill units for assembly horizontally on the façade
Please note:
The described under sill ventilation unit variant is equipped with a single room control system arranged in the unit for autonomous classroom operation. The supplied controllers contain the standard control parameters for operation according to our control description
School ventilation unit – under sill installation – master unit
Under sill ventilation unit TROX SCHOOLAIR-B-HV with supply and extract air function, rotary heat recovery unit and switchover option to secondary air operation (air quality dependent) as well as heating function for installation on an external wall below the window sill:
Units – dimensions and weights:
Width: approx. 2100 mm (without fixing straps)
Height: approx. 740 mm (without levelling feet area, additional distance for exhaust air suction)
Depth: approx. 403 mm (without façade sealing)
Weight: approx. 150 kg
FSL-CONTROL III controller
Including control system FSL-CONTROL III, as described below:
FSL-CONTROL III is described as stand-alone single room control equipment with a simple timer. Optional expansions, such as connection to the on-site central BMS via Modbus TCP / Modbus RTU, BACnet MS/TP or BACnet IP, humidity sensors, return flow temperature sensors, electromotive valve actuators or pressure-independent control valves are included in the product range, but must be replaced with the standard components in the following description. A room temperature signal is also required. Various room control panels and sensors are available for this purpose. The corresponding optional equipment text modules can be found in the appendix of the following standard equipment for room-autonomous operation. We recommend commissioning by our technical service. You will find related text modules below.
TROX control module FSL-CONTROL III (order code ...-C3-MA ...):
Real time clock (RTC)
Real Time Clock (RTC/real time clock) (order code ...-T/...):
CO2 sensor
CO22sensor (order code…/C/…):
Supply air temperature sensor
Supply air temperature sensor (order code .../Z/...):
Outdoor air temperature sensor
Outdoor air temperature sensor (order code .../A/...):
Water side components
Water-side components (order code .../HV-R-…/KV-R-…):
Optional control accessories
Optional equipment to increase the comfort of the FSL-CONTROL III:
TROX control panels for FSL-CONTROL III
Control panels with selector switch for surface mounting:
Control panel with selector switch, for surface mounting, type Honeywell
Control panel with selector switch, for surface mounting, type Thermokon
Control panels without selector switch for surface mounting:
Control panel without selector switch, for surface mounting, type Schneider
Control panel without selector switch, for surface mounting, type Thermokon
Room temperature sensor for surface mounting:
Room temperature sensor TROX RTF, surface mounting
Control panels without selector switch for flush mounting:
For manual operation of the ventilation units with a high-quality look and the matching design frame from a wide range of switch ranges, the unit is suitable for particularly design-oriented facilities.
Control panel without selector switch, for flush mounting, type Thermokon, switch from Berker S.1 range polar white
Control panel without selector switch, for flush mounting, type Thermokon, switch from Berker Q.3 range, white
Control panel without selector switch, for flush mounting, type Thermokon, switch from Busch Jäger future linear range, white
Further switch programmes on request.
Control panels without selector switch and without setpoint value adjuster for flush mounting:
Control panel without selector switch and without setpoint value adjuster, for flush mounting, type Thermokon, switch from Gira E2 range
Further switch programmes on request
Electromotive valve actuator:
As an alternative to the standard installed thermoelectric actuator
Pressure independent control valve:
As an alternative to the standard installed straight-way small valve
Interface for connection to central building management system (BMS) provided by others:
Modbus TCP interface including web server (order code .../MT/...)
To increase comfort, we recommend integration into a central building management system provided by others. FSL-CONTROL III offers the possibility to be connected to a central BMS provided by others using Modbus TCP protocol. Additionally incl. web server for simplified configuration, commissioning and remote monitoring of the device. The central BMS is not included in the supply package from TROX, only the interfaces listed above are available here.
BACnet IP interface including web server (order code .../BI/...)
To increase comfort, we recommend integration into a central building management system provided by others. FSL-CONTROL III offers the possibility to be connected to a central BMS provided by others using BACnet IP protocol. Additionally incl. web server for simplified configuration, commissioning and remote monitoring of the device. The central BMS is not included in the supply package from TROX, only the interfaces listed above are available here.
Modbus RTU (order code .../MR/...)
To increase comfort, we recommend integration into a central building management system provided by others. FSL-CONTROL III offers the possibility to be connected to a central BMS provided by others using Modbus RTU protocol. The central BMS is not included in the supply package from TROX, only the interfaces listed above are available here.
BACnet MS/TP (order code .../BM/...)
To increase comfort, we recommend integration into a central building management system provided by others. FSL-CONTROL III offers the possibility to be connected to a central BMS provided by others using BACnet MS/TP. The central BMS is not included in the supply package from TROX, only the interfaces listed above are available here.
Commissioning of the decentralised ventilation units
Commissioning / parameter setting of decentralised ventilation units without connection to the central building management system
Commissioning / parameter setting of decentralised ventilation units with connection to the central building management system
Instruction in operation and maintenance
SCHOOLAIR-B | – | HV | – | 2 | / | KM | / | 2100 × 740 × 403 | / | C3 | / | MA | – | T | / | MR | / | C | / | Z | / | A | / | HV | – | R | – | 0.4 | / | KV | – | R | – | 0.4 |
| | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |||||||||||||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 15 | 16 | 17 | 18 |
B | Under sill unit |
HV | High Volume |
2 | with 2-pipe heat exchanger |
KR | with condensate drain and water connection right |
C3 | with FSL-CONTROL III |
MA | Master construction |
T | with real time clock |
C | with CO2-sensor |
Z | with supply air temperature sensor |
A | with fresh air temperature sensor |
HV-R-0.40 | with straight-way valve (heating circuit) kvs 0.40 and lockshield |
Installation and commissioning
Share page
Recommend this page
Recommend this page by sending a link by mail.
Share page
Thank you for your recommendation!
Your recommendation has been sent and should arrive shortly.
Contact
We are here for you
Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
We are here for you
Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265