00136610_0

FKRS-EU with spring return actuator

00132715_0

Tested to VDI 6022

00132450_0

With TROXNETCOM as an option

00137627_0

CE compliant according to European regulations

00136515_0

FKRS-EU with fusible link for 72 °C or 95 °C

00136610_0
00132715_0
00132450_0
00137627_0
00136515_0
Configure now

Type FKRS-EU

Compact dimensions, ideal for restricted spaces

Small circular fire damper for the isolation of duct penetrations between fire compartments, available in ten nominal sizes

  • Nominal sizes: 100 – 315 mm
  • Low differential pressure and sound power level
  • Optional stainless steel casing or powder-coated casing for increased corrosion protection
  • Can also be used as an air transfer unit
  • Integration into the central BMS with TROXNETCOM
  • Universal installation options


Optional equipment and accessories

  • Electric actuator 24 V/230 V
  • Release temperature 72/95 °C
  • Duct smoke detector RM-O-3-D

v2.4.11.2
Updating order code
Save configuration
Calculate price
Casing
1
2
Damper blade variant
7
Construction variant
W
Accessories 1
ER
GL
TQ
WA
WE
Accessories 2
S0
0S
SS
A0
0A
SA
AS
Attachments
Updating technical data
Specification text: FKRS-EU/DE/160/Z00
Updating specification text

Circular fire dampers for the isolation of duct penetrations between fire compartments. Tested for fire resistance properties to EN 1366-2, with CE marking and declaration of performance according to the Construction Products Regulation. Ready-for-operation unit, which includes a fireresistant damper blade and a release mechanism. For mortar-based and dry mortarless installation into solid walls and ceiling slabs, lightweight partition walls with metal support structure, including fire walls, safety partition walls and walls to provide radiation protection; also for installation into timber stud walls and half-timbered constructions with cladding on both sides; for installation into lightweight partition walls with cladding on one side (shaft walls), with or without metal support structure. For dry mortarless installation on the face of solid walls and ceiling slabs, remote from solid walls and ceiling slabs, and remote from lightweight partition walls. For installation with flexible ceiling joint into lightweight partition walls with metal support structure and into fire walls; for dry mortarless installation with a fire batt into solid walls and ceiling slabs, and into lightweight partition walls with metal support structure, including safety partition walls and walls to provide radiation protection; also for dry mortarless installation with a fire batt into timber stud walls and half-timbered constructions with cladding on both sides. For mortar-based installation into wooden beam ceilings and modular ceilings (Cadolto system), and for installation with flexible ceiling joint into non-load-bearing solid walls and solid ceiling slabs. Casing length 400 mm, for the connection to ducts made of non-combustible or combustible materials. Thermal or thermoelectric release at 72 °C or 95 °C (warm air ventilation systems). Constructions with spring return actuator for opening and closing the fire damper independent of the nominal size and even while the ventilation system is running, e.g. for a functional test. Explosion-proof constructions for zones 1, 2, 21 and 22 with spring return actuator. Use as an air transfer unit in compliance with general building inspectorate licence no. Z- 19.18-2128 and with cover grilles both ends. Simple construction for dry mortarless installation with installation kit: ER, TQ, GL, WA, WE

SPECIAL CHARACTERISTICS
- Declaration of performance according to Construction Products Regulation
- Classification to EN 13501-3, up to EI 120 (ve, ho , i ↔ o) S
- Building inspectorate licence Z-56.4212-991 for fire resistance properties
- Complies with the requirements of EN 15650
- Tested to EN 1366-2 for fire resistance properties
- Hygiene complies with VDI 6022 part 1 (07/ 2011), VDI 3803 (02/2010), DIN 1946 part 4 (12/2008), and EN 13779 (09/2007)
- Corrosion protection according to EN 15650 in connection with EN 60068-2-52
- Closed blade air leakage to EN 1751, class 3
- Casing air leakage to EN 1751, class C
- Low differential pressure and sound power level
- Any airflow direction
- Integration into the central BMS with TROXNETCOM

MATERIALS AND SURFACES
.

CASING:
- Galvanised sheet steel
- Galvanised sheet steel, powder-coated RAL 7001
- Stainless steel 1.4301

DAMPER BLADE:
- Special insulation material
- Special insulation material with coating

OTHER COMPONENTS:
- Damper blade shaft in stainless steel
- Plastic bearings
- Seals of elastomer

VARIANTS
Casing: Basic construction
Damper blade variant: none
Construction variant: Release temperature 72 °C
Country: DE
Diameter: 160
Accessories 1: none
Accessories 2: Without
Attachments: Fusible link (Z00)

Standard construction

PRODUCT DATA:
Strategy: Given volume flow
Volume flow qv 290 m³/h
Airflow velocity v 4,01 m/s
Free area Afree 0,0160 m²
Pressure loss coefficient ζ 0,71
Total differential pressure Δpt 7 Pa

Acoustic results
General
LWA [dB(A)] 25
63Hz [dB] 45
125Hz [dB] 31
250Hz [dB] 28
500Hz [dB] 21
1kHz [dB] < 15
2kHz [dB] < 15
4kHz [dB] < 15
8kHz [dB] < 15
LWNC [dB] < 15
LWNR [dB] 17

Manufacture of the planning: TROX GmbH
Series: FKRS-EU/DE/160/Z00

Show complete text Hide complete text

Application

Application

  • Fire dampers of Type FKRS-EU, with CE marking and declaration of performance, for the isolation of duct penetrations between fire compartments in the event of a fire
  • To prevent the propagation of fire and smoke through ductwork to adjacent designated fire compartments

Special characteristics

  • Declaration of performance according to Construction Products Regulation
  • Classification to EN 13501-3, up to EI 120 (ve, ho, i ↔ o) S
  • Building inspectorate licence Z-56.4212-991 for fire resistance properties
  • Complies with the requirements of EN 15650
  • Tested to EN 1366-2 for fire resistance properties
  • Hygiene complies with VDI 6022 part 1 (07/2011), VDI 3803 (10/2002), DIN 1946 part 4 (12/2008), and EN 13779 (09/2007)
  • Corrosion protection according to EN 15650 in connection with EN 60068-2-52
  • Closed blade air leakage to EN 1751, class 3
  • Casing air leakage to EN 1751, class C
  • Low differential pressure and sound power level
  • Any airflow direction
  • Integration into the central BMS with TROXNETCOM

Classification

  • Class of performance to EN 13501-3, up to EI 120 (ve, ho, i ↔ o) S

Nominal sizes

  • 100, 125, 150, 160, 180, 200, 224, 250, 280, 315
  • L: 400 mm

Description

Variants

  • With fusible link
  • With spring return actuator
  • With cover grilles both ends as air transfer unit with general building inspectorate licence: Z-19.18-2128

Parts and characteristics

  • Dry mortarless installation into solid walls and ceiling slabs, lightweight partition walls, fire walls, and shaft walls using an installation block
  • Installation with wall face frame on the face of solid walls
  • Release temperature 72 °C or 95 °C (for use in warm air ventilation systems)
  • Approved installation orientation from 0° to 360°

Attachments

  • Limit switch for damper blade position indication
  • Spring return actuator for 24 V AC/DC or 230 V AC supply voltage
  • Network module for the integration with AS-i or LON networks

Accessories

  • Circular installation block ER
  • Square installation kit TQ
  • Wall face frame WA
  • Installation kit GL
  • Cover grille
  • Flexible connectors
  • Extension piece

Useful additions

  • Duct smoke detector RM-O-3-D
  • Duct smoke detector with airflow monitor RM-O-VS-D

Construction features

  • Rigid circular casing suitable for push fitting into cut circular holes without additional drilling and chiselling being required
  • Spigot connections with lip seal on both ends, suitable for ventilation ducts according to EN 1506 and EN 13180 plus non-standard but commercial nominal sizes 180, 224 and 280
  • Suitable for the connection of flexible connectors or cover grilles
  • The release mechanism is accessible and can be tested from the outside
  • One inspection access panel
  • Remote control with spring return actuator

Materials and surfaces

Casing:

  • Galvanised sheet steel
  • Galvanised sheet steel, powder-coated RAL 7001
  • Stainless steel 1.4301


Damper blade:

  • Special insulation material
  • Special insulation material with coating


Other components:

  • Damper blade shaft made of galvanised steel or stainless steel
  • Plastic bearings
  • Seals of elastomer


The construction variants with stainless steel or powder-coated casing meet even more critical requirements for corrosion protection. Detailed listing on request.

Standards and guidelines

  • Construction Products Regulation
  • EN 15650:2010 Ventilation for buildings – Fire dampers
  • EN 1366-2:1999 Fire resistance tests for service installations – Fire dampers
  • EN 13501-3:2010 Fire classification of construction products and building elements
  • EN 1751:1999 Ventilation for buildings – Air terminal devices

Maintenance

  • The functional reliability of the fire damper must be tested at least every six months; this has to be arranged by the owner of the ventilation system; functional tests must be carried out in compliance with the basic maintenance principles stated in EN 13306 and DIN 31051. If two consecutive tests, one 6 months after the other, are successful, the next test can be conducted one year later.
  • A functional test involves closing the damper blade and opening it again; with a spring return actuator this can be done via remote control
  • Fire dampers must be included in the regular cleaning schedule of the ventilation system.
  • For details on maintenance and inspection refer to the installation and operating manual

Technical information

  • Function
  • Technology
  • Quick sizing
  • Specification text
  • Order code
Construction with fusible link

Functional description

In the event of a fire, fire dampers shut automatically to prevent the propagation of fire and smoke through ductwork to adjacent designated fire compartments. In the event of a fire, the damper is triggered at 72 °C or at 95 °C (use in warm air ventilation systems) by a fusible link. The release mechanism is accessible and can be tested from the outside.

Construction with spring return actuator

Functional description

The spring return actuator enables the motorised opening and closing of the damper blade; it can be activated by the central BMS. In the event of a fire, the damper is triggered thermoelectrically at 72 °C or 95 °C (use in warm air ventilation systems). As long as power is supplied to the actuator, the damper blade remains open. If the supply voltage fails, the damper closes (power off to close). Motorised fire dampers can be used to shut off ducts. The torque of each actuator is sufficient to open and close the damper blade even while the fan is running. The spring return actuator is fitted with limit switches that can be used for capturing the damper blade position.

Nominal sizes100 – 315 mm
Casing length400 mm
Volume flow rate rangeUp to 770 l/s or up to 2770 m³/h
Differential pressure rangeUp to 1500 Pa
Operating temperatureAt least 0 – 50 °C **
Release temperature72 °C or 95 °C (for warm air ventilation systems)
Upstream velocity*≤ 8 m/s with standard construction; ≤ 10 m/s  with spring return actuator

* Data applies to uniform upstream and downstream conditions for the fire damper

** Temperatures may differ for units with attachments


Volume flow rate at differential pressure Δpst < 35 Pa

LWA [dB(A)] 253545253545
Nominal sizeV
mml/sm³/h
10022354379126157
125406587144234315
15070105150252378540
16080125180288450648
180105165235388587847
2001402102955047561062
2241702453456128821242
25021531544577411341602
280280405570100814582052
315360525735129618902646

The Easy Product Finder allows you to size products using your project-specific data.

You will find the Easy Product Finder on our website.


Circular fire dampers for the isolation of duct penetrations between fire compartments.

Tested for fire resistance properties to EN 1366-2, with CE marking and declaration of performance according to the Construction Products Regulation.

Ready-for-operation unit, which includes a fire-resistant damper blade and a release mechanism. For mortar-based installation and dry mortarless installation into solid walls and ceiling slabs, mortar-based installation into non-load-bearing solid walls with flexible ceiling joint, mortar-based and dry mortarless installation into lightweight partition walls with cladding on both sides, lightweight fire walls and lightweight shaft walls, and dry mortarless installation on the face of solid walls. For dry mortarless installation in lightweight partition walls with metal support structure and flexible ceiling joint; for dry mortarless installation in solid walls and ceiling slabs when using a fire batt; in lightweight partition walls with metal support structure and cladding on both sides.

Casing length 400 mm, for the connection to ducts made of non-combustible or combustible materials. Thermal or thermoelectric release at 72 °C or 95 °C (warm air ventilation systems).

Constructions with spring return actuator for opening and closing the fire damper independent of the nominal size and even while the ventilation system is running, e.g. for a functional test.

Simple construction for dry mortarless installation with installation kit: ER, TQ, GL, WA

Special characteristics

  • Declaration of performance according to Construction Products Regulation
  • Classification to EN 13501-3, up to EI 120 (ve, ho, i ↔ o) S
  • Building inspectorate licence Z-56.4212-991 for fire resistance properties
  • Complies with the requirements of EN 15650
  • Tested to EN 1366-2 for fire resistance properties
  • Hygiene complies with VDI 6022 part 1 (07/2011), VDI 3803 (10/2002), DIN 1946 part 4 (12/2008), and EN 13779 (09/2007)
  • Corrosion protection according to EN 15650 in connection with EN 60068-2-52
  • Closed blade air leakage to EN 1751, class 3
  • Casing air leakage to EN 1751, class C
  • Low differential pressure and sound power level
  • Any airflow direction
  • Integration into the central BMS with TROXNETCOM

Materials and surfaces

Casing:

  • Galvanised sheet steel
  • Galvanised sheet steel, powder-coated RAL 7001
  • Stainless steel 1.4301


Damper blade:

  • Special insulation material
  • Special insulation material with coating


Other components:

  • Damper blade shaft made of galvanised steel or stainless steel
  • Plastic bearings
  • Seals of elastomer


The construction variants with stainless steel or powder-coated casing meet even more critical requirements for corrosion protection. Detailed listing on request.

Technical data
  • Nominal sizes: 100 to 315 mm
  • Casing length: 400 mm
  • Volume flow rate range: up to 770 l/s or 2770 m³/h
  • Differential pressure: up to 1500 Pa
  • Operating temperature: at least 0 – 50 °C **
  • Release temperature 72 °C or 95 °C (for use in warm air ventilation systems)
  • Upstream velocity: ≤ 8 m/s with standard construction; ≤ 10 m/s * with spring return actuator


Note:

* Data applies to uniform upstream and downstream conditions for the fire damper

** Temperatures may differ for units with attachments

 

Downloads

product information

certificates

operation manuals

Installation video

In the past, openings for the installation of fire dampers in solid walls or ceiling slabs had to be of the exact size; only minimal tolerances were allowed, if at all. This has changed with fire batt solutions as they provide a new level of flexibility. With a fire batt, fire dampers can in fact be installed in openings that are much larger than the fire damper casing – the perimeter gap may be up to 400 mm wide. It is no longer a strict requirement that an installation opening fits the fire damper exactly.

Installation video  

Conversion kits are available to fit TROX fire dampers with a spring return actuator.

Type BLF230 (230 V AC)

Type BLF24 (24 V AC/DC)

Installation video  

FKRS-EU Mounting limit switch

FKRS-EU- Converting a BLF actuator to an explosion-proof actuator

FKRS-EU- Converting a BLF actuator to BFL actuator

Share page

Recommend this page

Recommend this page by sending a link by mail.

Fields marked with an (*) are required fields.

Share page

Thank you for your recommendation!

Your recommendation has been sent and should arrive shortly.

Contact

We are here for you

Visual contact Visual contact

Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Visual contact Visual contact

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

Contact

We are here for you

Visual contact Visual contact

Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

Attachment (max. 10MB)

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Visual contact Visual contact

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265